8.12 Size 8 KFU 610 (160 to 400 kW, 690 V)
Type
KFU 610
-180
-230
-280
-350
-400
-450
Size
8
Output motor side
Recommended motor shaft power
P
kW
160
200
250
315
355
400
Output current
I
A
eff.
180
230
280
350
400
450
Long-term overload current (60 s)
1)
I
A
eff.
270
350
420
530
600
675
Short-term overload current (1 s)
2)
I
A
eff.
330
420
510
630
720
750
Output voltage
U
V
eff.
Maximum input voltage, three-phase
Protection
-
-
Short circuit / earth fault proof
Rotary field frequency
f
Hz
±500 Hz
3)
Switching frequency
f
kHz
2, 4, 8
4)
Output, braking resistor (external)
Min. braking resistance
R
Ω
3,00
3,00
3,00
1,80
1,80
1,80
Recommended braking resistor
(U
dBC
= 770 V)
R
Ω
5,00
5,00
5,00
3,00
3,00
3,00
Input, mains side
Power supply current
6)
I
A
160
200
250
320
360
410
Mains voltage
7)
U
V
690 (for UL reduced: 600)
Mains frequency
f
Hz
50 (60)
Fuses
8)
I
A
250
315
350
450
500
550
Mechanical
Dimensions
HxWxD mm
1067 x 439 x 375
Weight approx.
m
kg
120
120
120
140
140
140
Ingress protection rating
-
-
IP20 (EN60529)
Connection terminals
A
mm
2
up to 2 x 240
Form of assembly
-
-
vertical
Ambient conditions
Energy dissipation (2 kHz
switching frequency)
P
W
3200
3950
4500
5500
6250
6900
Coolant temperature
T
n
°C
-25 … 45 (3K3 DIN IEC 721-3-3)
Storage temperature
T
L
°C
-25 ... 55
Transport temperature
T
T
°C
-25 ... 70
Rel. humidity
-
%
15 ... 85, not condensing
If required by the customer, the switching frequency may be increased if the output current is reduced at the same time.
Comply with the applicable standards and regulations for this operating point.
Output current
9)
Frequency inverter nominal power
Switching frequency
2 kHz
4 kHz
8 kHz
160 kW
180
180
180
200 kW
230
230
230
250 kW
280
280
280
315 kW
350
350
350
355 kW
400
400
400
400 kW
450
436
410
1)
Power reduction with torsional frequencies below 15 Hz
2)
Only with torsional frequencies above 15 Hz
3)
Depending on switching frequency
4)
Reduction of switching frequency possible on certain conditions
5)
As an option, the frequency inverter of this size is available without internal brake transistor
6)
Rated value with recommended motor power, 690V mains voltage and mains inductance UK=4%
7)
Note that, in addition to AC 3x690V connection, AC 3x400V connection is also required, see Chapter 4.3.
8)
Semiconductor fuses recommended (e.g. Bussmann Type 170M)
9)
Maximum current in continuous operation