KFU 210- / 410-
4
WARNING
!
Do not touch the heat sink of the frequency inverter during operation. Danger of burns due to
high surface temperatures.
Do not remove any covers of the frequency inverter during operation.
Please note that Küenle Antriebssysteme will not accept any responsibility for compatibility
with third-party products (e.g. motors, cables, filters, etc.). If you use the device in combination
with third-party products, you do so at your own risk.
The earth leakage current of the frequency inverter may exceed AC 3.5 mA or DC 10 mA.
Please note (according to EN61800-5-1): This product may cause direct current in the
protective earth conductor. Where residual current devices (RCD) or residual current monitors
(RCM) are used as a protection against direct or indirect contact, only RCDs / RCMs of Type
B are permissible on the power supply side of this product.
Do not touch electronic components or contacts.
Defective components must not be put into operation.
Any repair work may only be carried out by the manufacturer or persons approved/licensed by
the manufacturer.
Any repair work must be carried out by qualified electricians.
Except for modifications described in this document, the frequency inverter must not be
changed in any way.
Do not connect inappropriate voltage sources.
Keep the instructions accessible to the user.
NOTE
The frequency inverter may be connected to power supply every 60 s.
This must be considered when operating a mains contactor in jog operation mode. For commissioning
or after an emergency stop, a non-recurrent, direct restart is permissible.
NOTE
For more information about the range of functions of the frequency inverter and about operation,
maintenance and storage, refer to the co-applicable Operating Instructions.