5 Commissioning
The frequency inverter may be connected to power supply every 60 s. If the unit is switched on more frequently, it
may be damaged. This must be considered when operating a mains contactor in jog operation mode.
Disable release of frequency inverter; there may be no signals at inputs STOA (digital input S1IND/terminal
X210A.3) and STOB (digital input S7IND/terminal X210B.2).
Turn mains voltage on.
The frequency inverter will perform a self-test.
Other ways of commissioning (e.g. by means of optional communication modules) are described in the
co-applicable Operating Instructions.
5.1
Guided commissioning
NOTE
The frequency inverter may be connected to power supply every 60 s. If the unit is switched on more
frequently, it may be damaged. This must be considered when operating a mains contactor in jog
operation mode.
Disable release of frequency inverter; there may be no signals at inputs STOA (digital input
S1IND/terminal X210A.3) and STOB (digital input S7IND/terminal X210B.2).
Turn mains voltage on.
The frequency inverter will perform a self-test.
Before the start of guided commissioning, the motor should not have been operated, as a part of the
machine data is dependent upon the operating temperature.
If the unit is in "as-delivered" condition or after resetting the unit to the factory settings,
“SetUP” will be displayed automatically for guided commissioning. After successful
commissioning, the guided commissioning can be carried out again later via the sub-
menu CTRL.
Use the ENT key to switch to the CTRL sub-menu.
In the CTRL sub-menu, select the menu item “SetUP” and confirm by pressing the
ENT key.
Use the ENT key to select parameter Configuration 30.
Use the arrow keys to enter the number 110 or 410.
110: sensor-less control acc. to U/f characteristic
410: sensor-less, field-oriented control