Technical data of control terminals
Digital inputs
(X210A.3 … X210B.2): Low Signal: DC 0 V … 3 V, High signal: DC 12 V … 30 V,
Input resistance: 2.3 kΩ, response time: 2 ms (STOA and STOB: 10 ms), PLC compatible
Digital output
S1OUT
(X210B.3): Low Signal: DC 0 V… 3 V, High Signal: DC 12 V … 30 V,
Maximum output current: 50 mA, PLC compatible
Multifunction output MFO1
(X210B.4):
Digital output: Low Signal: DC 0 V… 3 V, High Signal: DC 12 V … 30 V, PLC compatible
Analog output: DC 19 … 28 V, maximum output current: 50 mA, pulse-width modulated (f
PWM
= 116 Hz),
Frequency signal: Output voltage: DC 0 V … 24 V, maximum output current: 40 mA,
maximum output frequency: 150 kHz
Multifunction input MF1
(X210B.6):
Analog signal: Input voltage: DC 0 … 10 V (R
i
=70 kΩ), Input current: DC 0 … 20 mA (R
i
=500 Ω),
Digital signal: Low Signal: DC 0 V … 3 V, High signal: DC 12 V…30 V, response time: 4 ms, PLC compatible
Conductor cross-section
:
The signal terminals are suitable for the following cable sizes:
with ferrule: 0.25 … 1.0 mm²
without ferrule: 0.14 … 1.5 mm²
4.2.2 External 24 V power supply X210A.1 & X210A.2
The bidirectional control terminals X210A.1/ X210A.2 can be used as a voltage output or voltage input. By
connecting an external power supply of DC 24 V ±10% to terminals X210A.1/X210A.2, the function of inputs and
outputs as well as the communication can be parameterized and maintained, even when mains voltage is off.
Requirements to be met by external power supply
Input voltage range
DC 24 V ±10%
Rated input current
Max. 1.1 A
Peak inrush current
Typically: < 25 A
External fuse
Via standard fuse elements for rated current, characteristic: slow
Safety
Safety extra low voltage (SELV) according to EN 61800-5-1
CAUTION
!
The digital inputs and the DC 24 V terminal of the electronic control equipment can withstand external
voltage up to DC 30 V. Avoid higher voltage levels. Higher voltages may destroy the unit.