SF000 No Error
SF001 The value entered for parameter
Rated Current
371
is too low. Correct the value.
SF002 The value for parameter
Rated Current
371
is too high, referred to parameters
Rated Mech. Power
376
and
Rated Voltage
370
. Correct the values.
SF003 The value entered for parameter
Rated Cosinus Phi
374
is wrong (greater than 1 or smaller than 0.3).
Correct the value.
SF004 The calculated slip frequency is negative. Correct the values entered for parameters
Rated Speed
372
and
Rated Frequency
375
.
SF005 The calculated slip frequency is too high. Correct the values entered for parameters
Rated Speed
372
and
Rated Frequency
375
.
SF006 The calculated total output of the drive is lower than the rated power. Correct the value entered for
parameter
Rated Mech. Power
376
.
SF007 The set configuration is not supported by the guided commissioning. In these instructions,
configurations 110 and 410 are described. Select one of these configurations for parameter
Configuration
30
.
Error messages after parameter identification
Code
Meaning / Measure
SF011
SF012
The main or leakage inductance measurement has failed because the motor has a high slip. Correct the
rated motor values in parameters 370, 371, 372, 374, 375 and 376. Carry out the guided commissioning
once again. In case an error message is displayed again, enter the value 110 for parameter
Configuration
30
(sensorless regulation according to U/f-characteristic) if value 410 was set so far.
Carry out the guided commissioning once again.
SF021
SF022
The measurement of the stator or rotor resistance did not deliver a plausible value. Check the cables at
the terminals of the motor and the frequency inverter for proper connection and check the contacts for
corrosion and safe contact. Repeat the parameter identification
SF026 Setup aborted