R60076.0002
–
Index 1
Page 18 / 24
Adjustable divider Z
Pegel conversion Z Puls (Z Divider: all OFF)
If the Z pulse have to be switched unchanged from the input to the output (no division, no
change in length and position), then the DIL switch position listed below must be chosen.
Divider [Z]
DIL4 (right 8-pole)
Comment
Binary value
1
2
3
4
5
6
7
8
1
2
4
8
16
32
64
12
8
OFF OFF OFF OFF OFF OFF OFF OFF
ZIN = ZOUT (ZERO_Z = Low)
The output at the level conversion can be set to zero (ZOUT = Low) with the control input X2(3)
ZERO_Z = High.
The function is active as long as there is a high level at the control input. The Z pulse can be
trimmed by switching.
Setting the Z Divider
The programming of the Z divider is subject to the same rules as the programming of the A/B
divider.
Divider [Z]
DIL4 (right 8-pole)
Comment
Binary value
Divider => 1: Binary value +1
1
2
3
4
5
6
7
8
1
2
4
8
16
32
64
12
8
ON OFF OFF OFF OFF OFF OFF OFF
1 : 2
OFF ON OFF OFF OFF OFF OFF OFF
1 : 3
ON ON OFF OFF OFF OFF OFF OFF
1 : 4
OFF OFF ON ON ON ON ON ON
1 : 253
ON OFF ON ON ON ON ON ON
1 : 254
OFF ON ON ON ON ON ON ON
1 : 255
ON ON ON ON ON ON ON ON
1 : 256
Location and width of the Z pulse
If the DIL switch DIL4 of the Z divider is completely set to OFF, the Z Pulse is forwarded from the
input directly to the output (see level conversion Z Puls).