KT-Elektronik
SOL3-7
02
Modbus-16-bit-adressing
0
Only with CO6 -> F01 – 1
CO6 -> F02 - 1: 16-bit-adressing,
CO6 -> F02 - 0: 8-bit-adressing
03
Modem function
0
CO6 -> F03 - 1 only with CO6 -> F01 – 1 and CO6 -> F08 - 1
04
Automatic modem
configuration
0
CO6 -> F04 - 1 only with CO6 -> F03 – 1and CO6 -> F08 - 1
05
Lock dial-upl
0
CO6 -> F05 - 1: No dial-up to GLT in case of error, only with CO6 -> F03 - 1
06
Dial-up also upon corrected
error
0
CO6 -> F06 - 1: 1: Dial-up to GLT also to indicate that an error has been corrected ,
only with CO6 -> F03 - 1
07
Control system monitoring
CO6 -> F07 - 1: Resetting all level bits to “autonomous“ when there is no
communication, nur mit CO6 -> F01 - 1
08
Text message (SMS )
CO6 -> F08 - 1: Sending of text message active (SMS) active
F Function block number, FD Factory default
Parameter lists
PA1: Heating circuit
Parameter description
Range of value FD
Comment
Gradient, flow
0,2 to 3,2
0,4
With CO1 -> F05 – 1: 0,2 bis 1,0 (WE 1,0)
Level (parallel shift)
–30 to 30 °C
0 °C
Min. flow temperature
5 to 130 °C
20 °C
Max. flow temperature
5 to 130 °C
50 °C
With CO1-> F05 – 1 : 5 bis 50 °C (WE 50 °C)
4-point-characteristic
Press rotary pushbutton to modify parameters
Point 1: Outdoor temperature
–40 to 50 °C
1: -15 °C
2: -5 °C
3: 5 °C
4: 15 °C
Outdoor temperatures of the points 2, 3, 4 are marked by
squares below the numbers 2, 3, 4.
Point 1: Flow temperature
5 to 130 °C
1: 70 °C
2: 55 °C
3: 40 °C
4: 25 °C
Flow temperatures of the points 2, 3, 4 are marked by
squares below the numbers 2, 3, 4.
Point 1: Reduced flow
temperature
5 to 130 °C
1: 60 °C
2: 40 °C
3: 20 °C
4: 20 °C
Reduced flow temperatures of the points 2, 3, 4 are marked
by squares below the numbers 2, 3, 4.
Point 1: Return flow temp.
5 to 90 °C
1 to 4:
65 °C
Return flow temperatures of the points 2, 3, 4 are marked
by squares below the numbers 2, 3, 4.
Outdoor temp. deactivation
value in rated operation
0 to 50 °C
22 °C
Outdoor temp. deactivation
value in reduced operation
–20 to 50 °C
15 °C
activation value in rated operati. –20 to 5 °C
–15 °C
Day set point for flow temp.
5 to 130 °C
50,0 °C
Only for flash adaptation without outdoor temp. sensor
Night set point for flow temp.
5 to 130 °C
30,0 °C
Only for flash adaptation without outdoor temp. sensor
Day set point for room temp.
0 to 40 °C
20°C
Night set point for room temp.
0 to 40 °C
15°C
PA3: Solar circuit
Parameter description
Range of value FD
Comment
Min. ON time collector pump
0 to 1800 s
60s
Min. OFF time collector pump
0 to 1800 s
180s
Max. storage tank temperature
switch OFF condition
20 to 160 °C
60°C
Parameter exists for storage tank 1 and 2;
to indicate storage tank 2, symbol '2' displayed additionaly
Max. storage tank temperature 20 to 160 °C
58°C
Parameter exists for storage tank 1 and 2;
KA_37387_SOL3-7_EN004