Quick installation and operating manual
KT-Elektronik
10
Temperature difference
controller
0
10K
2
7
CO3 F10 = 1 Temperatur difference controller active
Function block parameter
Temperatur difference set point / -30 bis 160°C
Reference input / Terminal number 1...9
Controlled input / Terminal number 1...9
F Function block number, FD Factory default
CO4: DHW heating
F
Function
FD
Comment
14
Thermal desinfection
0
CO4 -> F14 - 1 only with CO4 -> F01 - 1
Function block parameters:
Day of week / 1, 2, …, 7, 1–7 (3)
Start time / 00:00 to 23:45 (00:00)Stop time / 00:00 to 23:45 (04:00)
Desinfection temperature / 60 to 90 °C (70 °C)
Set point boost / 0 to 50 °C (10 °C)
F Function block number, FD , Factory default
CO5: System-wide functions
F
Function
FD
Comment
01
02
03
Sensor initialisization
1
Irrelevant of the function block setting: Pt 1000
04
Summer mode
0
CO5 -> F04 - 1: Activation of time-controlled summer mode
Function block parameters:
Start summer mode / 01.01 to 31.12 (01.06)
No. of days until activation / 1 to 3 (2)
Stop summer mode / 01.01 to 31.12 (30.09)
No. of days until deactivation / 1 to 3 (1)
Outdoor temperature limit for summer mode / 0 to 30 °C (18 °C)
05
Delayed outdoor tempera-
ture adaptation when
temperature decreases
0
06
Delayed outdoor tempera-
ture adaptation when
temperature increases
0
CO5 -> F05, 06 - 1: Function block parameters::
Delay per hour
/ 1 to 6 °C/h (3 °C/h)
08
Automatic summer / winter
time
1
09
Frost protection program II
1
CO5 -> F09 - 0: Frost protection program I (restricted Frostprotection)
Function block parameters:
Frost protection limit / –15 to 3 °C (3 °C)
CO5 -> F09 - 1: Frost protection program II
Function block parameters:
Frost protection limit / –15 to 3 °C (3 °C)
19
Temperature monitoring
0
CO5 -> F19 - 1: Temperature monitoring active
20
Sensor calibration
1
CO5 -> F20 - 1: Adjusting all sensor calibration values
CO5 -> F20 - 0: Deleting all adjusted sensor calibration values
21
Locking manual level
0
CO5 -> F21 - 1: In switch position (manual level) automatic mode applies
22
Locking the rotary switch
0
CO5 -> F22 - 1: 1: Rotary switch without function – Access after entering key number
still possible.
F Function block number, FD Factory default
CO6: Modbus
F
Function
FD
Comment
01
Modbus
1
CO6 -> F01 - 1: Modbus active
16