background image

 

- 16 - 

1.5.4 Rear panel instruction 

 

Fig.1-4 YDC9310H/S

 

Rear Instruction 

1)  AC input

 

2)  Maintenance bypass switch (covered)

 

3)  Handle

 

4)  Output

 

5)  Input

 

6)  Dry contact

 

7)  RS232   

8)  RS485

  

9)  Intelligent slot

 

10)  Parallel slot

 

11)  External battery connector

 

Summary of Contents for YDC9300-0.8

Page 1: ...gh frequency online UPS designed by our R D team who is with years of designing experiences on UPS With excellent electrical performance perfect intelligent monitoring and network functions smart appe...

Page 2: ...e UPS input and make sure the UPS is completely off before moving the UPS or reconfigured the connection otherwise there will be potential electric shock 3 For the sake of human being safety please we...

Page 3: ...will not be free of operation for long time Storage temperature of UPS with internal battery is 20 to 55 extended backup model without internal battery is 40 to 70 10 Taking out the UPS or batteries f...

Page 4: ...n 11 1 5 4 Rear panel instruction 16 2 Installation 18 2 1 Unpack checking 18 2 2 Installation procedure 18 2 2 1 Installation note 18 2 2 2 Installation 19 2 3 Connection of parallel system 23 3 Oper...

Page 5: ...short circuit 28 3 4 UPS monitoring 29 3 5 LCD operation menu 29 3 5 1 Main menu switching 29 3 5 2 Submenu switching 29 3 5 3 Priority of info displayed on LCD 29 4 Maintenance 30 4 1 Fan maintenanc...

Page 6: ...ystem telecom system etc 1 2 Product range Capacity 10kVA 15kVA 20kVA Model Standard model Extended model Standard model Extended model Remarks with internal battery External battery with internal bat...

Page 7: ...iagnostics and protections are featured in Intelligent battery management which extends battery life LCD panel and LED indicators clearly indicate the system status and parameters such as input output...

Page 8: ...l 1 Five green LED and one red LED 2 LCD control panel which can display two lines of Chinese or four line of English 3 Button On Off ESC Enter and Left Right ON OFF ESC ENT BYPASS RECT INV OUTPUT FAU...

Page 9: ...ut LCD display content 1 Running parameters Input voltage frequency output voltage frequency current temperature inside UPS battery charging fully charged battery voltage 2 Alarm information priority...

Page 10: ...parameter Turn to another menu or parameter UPS Messages reference table Explain Content Initialization CurState Init No export No Out At bypass Bypass Rectifier working Mains Battery invert Battery B...

Page 11: ...he ENT then the data info status info setting info command control can be selected by pressing the right or left arrow button and checking the details by pressing 5 Select and confirm the data info to...

Page 12: ...menu Fig 15 status info Fig 16 Alarm info Fig 17 type info Fig18 code info Fig19 version info Figure INVERT 220 0V 50 0HZ Figure BUS VOLT 390V 390V Figure PARALLEL ID 01 STATUS State Alarm Fault Rate...

Page 13: ...ystem setting menu then see Fig23 Fig28 Fig 23 system setting Fig 24 system setting Fig 25 system setting Fig 26 System setting Fig 27 System setting Fig 28 System setting Setting User set System set...

Page 14: ...sting Fig 39 Turn on off delay Fig 40 Battery capacity self test Setting Parallel Set ID 1 P Amount 1 Setting Parallel Set P Redund 0 LBS NO LBS Setting Battery Set EOD 1 60 Batt Num 10 Setting Batter...

Page 15: ...Fig 44 overload due to shutdown Fig 45 no output due to shutdown Fig 46 switch times Warning Set no Echo 31 Warning Set Error 31 Warning Interrupt switch prompt Sure Ent No ESC Warning Off will cause...

Page 16: ...l instruction Fig 1 4 YDC9310H S Rear Instruction 1 AC input 2 Maintenance bypass switch covered 3 Handle 4 Output 5 Input 6 Dry contact 7 RS232 8 RS485 9 Intelligent slot 10 Parallel slot 11 External...

Page 17: ...17 Fig 1 5 YDC9315 YDC9320 Rear Instruction 1 Input 2 Output 3 AC input 4 Maintenance bypass switch 5 Dry contact 6 RS232 7 RS485 8 Intelligent slot 9 Parallel slot 10 External battery connector...

Page 18: ...as to keep the ventilation in good conditions avoid temperature of components inside getting high Keep the UPS away from high temperature water flammable gas erosive gas dust direct sunlight explosive...

Page 19: ...batteries either 2 The breaker onto battery cabinet should be off 3 Take out the connection box and remove the cover of terminals use multi meter to make sure there is no DC voltage at the battery te...

Page 20: ...20 BAT BATN BAT L N N C B A BAT 8 9 10 BAT 8 9 10 Fig 2 2b YDC9310H External battery connection BAT 8 9 10 BAT 8 9 10 BAT BATN BAT L N N C B A Fig 2 2c YDC9315 9320 External battery connection...

Page 21: ...he cover of the terminals see Fig 2 3 then follow them to connect the cables correctly Fig 2 3a YDC9310S I O terminals connection Fig 2 3b YDC9310H I O terminals connection Fig 2 3c YDC9315 9320 I O t...

Page 22: ...the UPS communication cables 1 RS 232 cable provided in accessories can be used to connect the UPS with PC 2 Follow step below is to install SNMP if purchased A Remove the cover of SNMP slot at UPS r...

Page 23: ...llel the copper wires required to connect with each UPS is minimum 5AWG but the main wire for linking all the UPS in parallel should be N 5AWG N refers to the number of the UPS in parallel Make sure t...

Page 24: ...3 Battery mode In AC mode if the AC is absence or beyond normal range the rectifier and charger will stop working the loads will be powered by battery bank of which energy goes through inverter circui...

Page 25: ...work in ECO mode if the load has no strict requirement on the power purity and the UPS can stay in bypass mode normally If the AC is beyond normal range the UPS will transfer back to inverter mode Th...

Page 26: ...ed backup model only 3 2 3 Start AC available 1 Press the On button and hold it for 1s until hearing a beep wait for a few seconds the bypass indicator will be off the inverter indicator will be on se...

Page 27: ...y indicator stops blinking and the UPS will recover to status before testing If there are some problems with the batteries the LCD will show details CAUTION The battery status info will be re fresh ev...

Page 28: ...exhausted When AC recovers the UPS will start inverter automatically If the UPS was shut down manually in battery mode when AC recovers it will remain in Bypass mode which means you can not start the...

Page 29: ...he ESC to return to main menu 3 Parameter which has been selected and changed will be highlighted Press arrow button to change the value and press the ENT to confirm the value Once confirmed it will n...

Page 30: ...ons 1 The most proper working temperature is 15 to 25 Celsius degree 2 Avoid small discharging current Don t let UPS work in battery mode continuously for 24 hours 3 Charge battery for at least 12 hou...

Page 31: ...mode make sure it is normal on the contrary please find out the cause 4 5 Function checking Do function checking once every 6 months 1 Press the off button to see if the buzzer and indicators and the...

Page 32: ...g Input AC is beyond normal range Pay attention to the backup time if the UPS is in battery mode 6 Buzzer beeps twice every second the LCD shows output overload UPS overload Disconnect some loads 7 Fa...

Page 33: ...start UPS 12 Long beeps fault indictor on the LCD shows rectifier fault inverter fault auxiliary power fault output fault Fault inside UPS Contact distributor 13 Abnormal sound or smell Fault inside U...

Page 34: ...ing Connection between PC RS232 port and UPS RS232 port PC UPS RDX 2 TX 2 TDX 3 RX 3 GND 5 GND 5 Available function of RS232 Monitor UPS power status Monitor UPS alarm info Monitor UPS running paramet...

Page 35: ...ad input THDV 1 battery Battery number 2 8 10 12V Battery type VRLA Charge model Boost charge or float charge auto switch Charge time Boost charge up to 20Hr Max Charge current A 1A S 6A H output Outp...

Page 36: ...IEC 62040 2 MTBF 250 000Hr 1 1 400 000Hr MTTR 30min Isolation resistance 2M 500Vdc Isolation intension 2820Vdc 3 5mA 1min Surge Meeting IEC60664 1 1 2 50uS 8 20uS 6kV 3kA Protection IP20 Strike Meeti...

Page 37: ...E F Input 1 main 0 battery 4 5 6 7 C D E F charging 2 3 6 7 A B C E F P battery boost charging 1 3 5 7 9 B D F N battery boost charging 8 9 A B C D E F Battery self testing 4 5 6 7 C D E F 00 shutdow...

Page 38: ...rectifier over current 8 9 A B C D E F Assistant supply 1 fault 4 5 6 7 C D E F Assistant supply 2 fault 2 3 6 7 A B C E F Input SCR fault 1 3 5 7 9 B D F discharge SCR fault 8 9 A B C D E F Charge S...

Page 39: ...F CAN communication fault 1 3 5 7 9 B D F Current no equality for parallel 8 9 A B C D E F Bypass phase wrong 4 5 6 7 C D E F Sync fault 2 3 6 7 A B C E F Bypass over track 1 3 5 7 9 B D F Bypass over...

Reviews: