Installation and putting into operation of the BNA…EX bypass 
level indicator in explosion risk areas 

The  BNA…EX  bypass  level  indicator  is  mounted  on  the  container  in  which  the  fluid 
level  is  to  be  monitored  by  means  of  the  planned  process  connections  (1)  in  the 

vertical position. Use properly fitting gaskets (2), bolts (3), washers (4) and nuts (5) for installation. 
Make  sure  the  gaskets  used  are  corrosion-proof  as  required.  Install  cutoff  fixtures  between  the 
container  and  the  bypass  device  as  required.  Comply  with  the  limit  values  stipulated  for  the 
BNA…EX  bypass  level  indicator  for  reasons  of  explosion  protection  and  within  the  framework  of 
the intended use of the device and the applicable laws and regulations (proof of inherent safety). 
Compliance  with  any  "Special  Conditions"  stipulated  in  such  laws  or  regulations  is  of  particular 
importance. 
 

 

Please  comply  with  the  maximum 
torque  ratings  of  the  bolts  /  screws 
used when tightening them down. 

Use  suitable  gaskets.  Make  sure  the 

gasket  material  is  resistant  to  the  medium  and  its 
vapours  as  well  as  to  the  expected  temperature  and 
pressure loads. 
 

Installation of float 

1.  Remove the bottom flange (7) and insert the float 

(6)  into  the  tube  from  the  bottom.  (See  marking 
"TOP"). 

2.  Place  gasket  (9)  on  the  bottom  flange.  Replace 

the  bottom  flange  and  tighten  it  down  with  bolts 
(8). 

 

Attention! 

A  fall  protection  device  is  located  at  the 
bottom  and  top  chamber  end  (e.g. 
flange)  consisting  of  a  spring  supporting 

a  PTFE  disc.  This  device  serves  to  cushion  a  float 
impact and prevent metal elements from coming into 
contact.  Be  careful  not  to  damage  the  fall  protection 
device when inserting and removing the float. 
 
 
 

 

 

6

9

1

3

7

2

4

5

8

M

L1

L2

L = Bottom dead leg dependent on S.G. of liquid

Fig. 1

 

 

 

Summary of Contents for BNA EX Series

Page 1: ...Rev 7 16 03 2015 Manual de Instru es e de Montagem KEMA 02ATEX2106 X Por favor guarde esta informa o para uso futuro Please retain for future usage BNA EX Montage und Betriebsanleitung Mounting and op...

Page 2: ......

Page 3: ...OI_BNA_EX_pt_en doc...

Page 4: ...OI_BNA_EX_pt_en doc...

Page 5: ...OI_BNA_EX_pt_en doc...

Page 6: ...OI_BNA_EX_pt_en doc...

Page 7: ...OI_BNA_EX_pt_en doc...

Page 8: ...ratura 11 Dados de press o 11 English 12 Symbol legend 12 Safety information 12 Danger 13 Application and field of use 13 Attention 13 Removal of transport packaging and transport safety devices 13 In...

Page 9: ...vor leia estas Instru es antes de instalar e utilizar indicadores de n vel tipo Bypass BNA EX Este Manual destina se a profissionais que realizam a montagem a instala o e a configura o As normas de se...

Page 10: ...rui o dos indicadores de n vel tipo Bypass e causar danos pessais e materiais Todos os materiais do tubo Bypass e do flutuador devem ser resistentes ao meio a ser monitorado Os valores m ximos indicad...

Page 11: ...favor consulte os valores de torque dos parafusos Deve se aplicar selagens apropriadas Verificar se o material de selagem contra o meio e os seus vapores a temperatura e cargas de press o previstas s...

Page 12: ...segundo os folhetos AD Para eliminar o risco de explos o devido ao aquecimento aplicam se os seguintes requisitos para a opera o de aquecimento e para a transfer ncia de calor 1 A temperatura de trans...

Page 13: ...transdutores MG A descri o que se segue pretende ser apenas um guia para uma op o de montagem em determinado local Por favor leia tamb m as instru es de instala o e funcionamento de equipamento desmo...

Page 14: ...mplo de montagem MNAV montagem do interruptor magn tico em barra de reten o A montagem deste interruptor magn tico feita em uma barra de reten o separada 1 Retirar a barra de reten o 1 desapertando os...

Page 15: ...l tipo Bypass s pode ser garantida com a utiliza o de acess rios originais KSR Kuebler e pe as de reposi o Solu o de problemas Na tabela a seguir est o listados os problemas mais comuns e as contramed...

Page 16: ...cos a o inoxid vel 180 C temperatura m dia SG com escala alum nio gravado VSG com escala a o inoxid vel gravado especifica o somente se a op o estiver dispon vel S se pode instalar interruptores magn...

Page 17: ...9 21 OI_BNA_EX_pt_en doc extremidade da solda S S 3 4 Tipo b sico BNA...

Page 18: ...sico Flutuador cilindro Execu o sem gr nulos Tipo b sico Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 Code 7 Z V S 250 16 60 1000 Code 7 Sistema magn tico Code 6 Densidade em kg m Code 5 Temperatura em...

Page 19: ...m xima Temperatura ambiente m xima no dispositivo de avalia o MRA MRAN MNAV MRK MNKV T1 320 C 320 C 50 80 C A temperatura ambiente m xima do dispositivo de avalia o deve ser respeitada A mesma n o de...

Page 20: ...G or MG Safety information Read these instructions before installing the BNA EX and putting them into operation These instructions are intended for the specialists in charge of mounting installation a...

Page 21: ...vels may result in malfunction or destruction of the bypass level indicator as well as to personal injury and property damage All of the materials used in the bypass chamber and float must be resistan...

Page 22: ...nce with any Special Conditions stipulated in such laws or regulations is of particular importance Please comply with the maximum torque ratings of the bolts screws used when tightening them down Use...

Page 23: ...ch this construction is exposed To eliminate the risk of explosion caused by the heating system the following requirements apply to operation of the heating system and the heat carrying medium 1 The t...

Page 24: ...evel Sensor MG The description provided here must be considered as being a means of orientation for the mounting on possibility provided by location specific conditions Please also refer to the assemb...

Page 25: ...witch must then be mounted the other way around with the type plate upside down Example of installation MNAV mounting of magnetic switch on a retainer rod This magnetic switch is attached to a retaine...

Page 26: ...level indicator can only be guaranteed if original KSR Kuebler accessories and replacement parts are used Error Search The following table lists the most frequent causes of error and the necessary cou...

Page 27: ...ature MNKV Magnetic Roller Indicator Edelstahl 180 C ambient temperature SG with Scale Aluminium engraved VSG with Scale Stainless steel engraved Only specification if option is available Only BGUV ma...

Page 28: ...Titanium max 16 bar Basic type Cylindrical floats Design without beads Basic type Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 Code 7 Z V S 250 16 60 1000 Code 7 magnet system Code 6 density in kg m Code...

Page 29: ...processing and display equipment MRA MRAN MNAV MRK MNKV T1 320 C 320 C 50 80 C Avoid temperatures in excess of the maximum ambient temperature allowed for the installed processing and display equipmen...

Page 30: ..._en doc 22 21 KSR KUEBLER AG Adressen KSR KUEBLER Niveau Messtechnik AG Heinrich Kuebler Platz 1 D 69439 Zwingenberg Neckar Tel 49 06263 870 Fax 49 06263 87 99 http www ksr kuebler com e Mail info ksr...

Reviews: