7 Servicing/Maintenance
34 of 64
MK
WARNING
Insufficient stability
Risk of crushing hands and feet!
▷
During assembly/dismantling, secure the pump (set)/pump parts to prevent
tilting or tipping over.
A regular maintenance schedule will help avoid expensive repairs and contribute to
trouble-free, reliable operation of the pump, pump set and pump parts with a
minimum of servicing/maintenance expenditure and work.
NOTE
All maintenance work, service work and installation work can be carried out by KSB
Service or authorised workshops. For contact details please refer to the enclosed
"Addresses" booklet or visit "
www.ksb.com/contact
" on the Internet.
Never use force when dismantling and reassembling the pump set.
7.2 Servicing/Inspection
7.2.1 Supervision of operation
DANGER
Impermissibly high temperatures
Explosion hazard!
Damage to the pump!
▷
Prolonged operation against a closed shut-off element is not permitted
(heating up of the fluid).
▷
Observe the temperature limits in the data sheet and in the section on
operating limits. (
ð
Section 6.2, Page 29)
DANGER
Excessive temperatures as a result of bearings running hot or defective bearing
seals
Explosion hazard!
Fire hazard!
Damage to the pump set!
Risk of burns!
▷
Regularly check the lubricant level.
▷
Regularly check the rolling element bearings for running noises.
CAUTION
Fluid level below the specified minimum
Damage to the pump set by cavitation! Dry running of the plain bearings!
▷
Never allow the fluid level to drop below the specified minimum.
While the pump is in operation, observe and check the following:
▪
The pump must run quietly and free from vibrations at all times.
▪
Check the shaft seal.
▪
Check the static sealing elements for leakage.