7
Waiting time before stopping
Parameter: 3-4-3-5
8
Waiting time before system start-up
Parameter: 3-4-3-3
Table 21: Parameters required for settings
Parameter
Description
Factory Set 1/
Factory Set 2
Setting range/options Access
Reference to
3-4-3-1
Enable/disable sleep mode
1 / 1
See selection list
Customer
3-4-3-2
Difference between feedback and
setpoint to start
0 / 0
0..6500 [3-2-2-1]
Customer
3-4-3-3
Time delay between signal on digital
input and start of motor
1 / 1
0.1..60 [s]
Customer
3-4-3-4
Frequency limit to enter sleep mode 50 / 50
3-6-1-2..3-6-1-3 [%]
Customer
3-11-4-1
3-4-3-5
Time delay to stop PumpDrive
10 / 10
0.1..30 [s]
Customer
3-4-3-6
Time delay after detection of
minimum flow (min. Q) level
60 / 60
45..360 [s]
Service
3-4-3-7
Difference between feedback and
setpoint to start test pulses
2 / 2
0..9999 [3-2-2-1]
Service
3-4-3-8
Test pulse amplitude
2 / 2
0..9999 [3-2-2-1]
Service
3-4-3-9
Pulse time
10 / 10
3..30 [s]
Service
3-2-2-1
Physical unit for setpoint
1 / 1
See selection list
Service
3-6-1-2
Low motor frequency limit
0 / 0
0..100 [%]
Customer
3-11-4-1
3-6-1-3
High motor frequency limit
100 / 100
0..100 [%]
Customer
3-11-4-1
3-11-4-1
Maximum output frequency
60 / 60
1..600 [Hz]
Factory
Table 22: Selection list for parameters
Selection list for parameters
3-4-3-1
3-2-2-1
1 – Disabled
1 - %
18 - W/m
2
35 - lb/min
2 – Enabled
2 -
19 - m/s
36 - lb/h
3 - Hz
20 - ft/s
37 - CFM
4 - kW
21 - l/s
38 - ft
3
/s
5 - kWh
22 - l/min
39 - ft
3
/min
6 - hex
23 - l/h
40 - ft
3
/h
7 - mA
24 - kg/s
41 - mbar
8 - A
25 - kg/min
42 - bar
9 - V
26 - kg/h
43 - Pa
10 - s
27 - m
3
/s
44 - kPa
11 - h
28 - m
3
/min
45 - m lc
12 - °C
29 - m
3
/h
46 - m Hg
13 - K
30 - GPM
47 - in Hg
14 - 1/min
31 - gal/s
48 - ft Hg
15 - m
32 - gal/min
49 - psi
16 - ft
33 - gal/h
50 - lb/in
17 - HP
34 - lb/s
8.7.4 Digital inputs
PumpDrive is equipped with six digital inputs (24 V process level).
Inputs 1 and 6 are assigned a fixed function:
▪
Digital input 1: Start/Stop command for single-pump drive, enable command in
multiple pump configuration
▪
Digital input 6: Changeover to multi-pump operation (not required for Hya-Solo
DV)
Table 23: The functions of inputs 2 to 5 are user-definable:
Parameter
Description
Factory setting
Setting range/options
Access
3-7-1-2
Function of digital input 2
7
See selection list
Customer
3-7-1-3
Function of digital input 3
10
See selection list
Customer
8 Operating the Pressure Booster System
Hya®-Solo DV
39 of 56