5.9.2 Connecting the control terminals
DANGER
Failure to interrupt power supply
Danger to life!
▷
Pull the mains plug or disconnect all electrical connections and secure against
accidental start-up.
NOTE
The housing cover must not be opened.
Non-compliance will result in forfeiture of any and all warranty claims.
The control terminals are located underneath the control panel.
This must be removed as follows.
1. Remove the cross-head screws on the L-shaped cover for the control cable and
remove the cover.
2. Remove the cross-head screws on the control panel and remove the control
panel.
NOTE
The screws fastening the cover of the mains and motor terminal box must be tightened to
a torque of 1.2 Nm to ensure that the device has IP55 enclosure protection.
The control terminal assignment is shown below.
The maximum cable cross-sections (wire size) which can be connected to the control
terminals of terminal strip P4 and terminal strip P7 are:
Table 6: Max. cable cross-sections to be connected to control terminals
Control
terminals
Rigid and flexible cables
Flexible cable with wire end sleeve
Terminal strip
P4
0.2 - 1.5 mm
2
0.75 mm
2
Terminal strip
P7
0.2 - 2.5 mm
2
0.25 - 1.5 mm
2