First, enter the customer password. (
8.7.2 Changing the controller settings
The PI controller of the frequency inverter is optimised when leaving the factory,
therefore no changes are required.
Should a process-related adjustment of the PI controller be necessary, check/change
the factory settings in accordance with the following table:
Table 18: Main parameters of the PI controller:
Parameter
Description
Factory Set 1/
Factory Set 2
Setting range/options Access
Reference to
3-9-1-1
Enable/disable PI controller
1 / 1
See selection list
Customer
3-9-1-2
PI proportional gain - kp
1 / 1
Customer
3-9-1-3
PI integral time
1 / 1
0..60 [s]
Customer
3-9-1-4
Process PI sense
1 / 1
See selection list
Customer
3-9-1-5
Process type of PI control
1 / 1
See selection list
Customer
3-9-1-6
PI automatic recognition function (PI
Auto Detect)
2 / 2
See selection list
Customer
3-6-1-2
Low motor frequency limit
0 / 0
0..100 [%]
Customer
3-11-4-1
3-6-1-3
High motor frequency limit
100 / 100
0..100 [%]
Customer
3-11-4-1
3-11-4-1
Maximum output frequency
60 / 60
1..600 [Hz]
Factory
Table 19: Selection list for parameters
Selection list for parameters
3-9-1-1
3-9-1-4
3-9-1-5
3-9-1-6
1 – Disabled
1 – Negative
1 – Const Pressure
1 – Disabled
2 – Enabled
2 - Positive
2 – Variable Press
2 – Enabled
3 – Constant Flow
4 – Other Setpoint
Table 20: Additional information on parameters
Process setting
3-9-1-2
Adjusting the proportional gain
e.g. open hydraulic circuit - pressure control
kp __________
e.g. closed hydraulic circuit - differential pressure control
kp __________
3-9-1-3
Adjusting the integral component
e.g. open hydraulic circuit - pressure control
Tn __________
e.g. closed hydraulic circuit - differential pressure control
Tn __________
3-9-1-4
Negative direction of action: actual value decreasing – speed is to increase
Positive direction of action: actual value decreasing – speed is to decrease
3- 9- 1-5
1 – Constant pressure/differential pressure at the sensor measuring location
2 – Variable pressure/differential pressure activates the dynamic pressure
compensation function
3-9-1-6
Automatic controller recognition when a signal is connected to the actual value
source