4 Description
16 of 48
Hya-Duo D FL Compact
– Tank with inlet device and flushing device, overflow monitoring and dry
running monitoring
2)
▪
Vibration damping
Installation
▪
Stationary dry installation
Drive
▪
Three-phase asynchronous motor
▪
380 / 420 V, 50 Hz
▪
2 poles
▪
Enclosure IP55
▪
Efficiency class IE3 to IEC 60034-30
▪
Soft starter for each pump
▪
Pressure-controlled starting and flow-controlled stopping
Automation
▪
Electro-mechanical control system, IP54
▪
Timer
▪
Manual-automatic selector switch
▪
Phase monitoring relay
▪
In automatic mode, the motor protection circuit only outputs an alert.
▪
Terminal strip/terminals with identification for all connections
▪
Pressure switch or remote ON/OFF, monitored for broken wires and short circuit
▪
Circuit diagram to VDE and parts list for electric parts
Indication via indicator lamps:
▪
Colour LED indicating lack of water (red)
▪
Colour LED indicating a fault (amber)
▪
Colour LED indicating readiness for operation (green)
▪
Colour LED indicating operation started by pressure switch or remote ON/OFF
(white)
Indication via volt-free isolating terminals:
▪
Lack of water
▪
Overflow
▪
Position of manual-automatic selector switch
▪
Pump control via pressure switch or remote ON/OFF
▪
General fault message
▪
Drinking water stop
Monitoring for broken wires and monitoring for short circuit:
▪
> 10.3 kΩ: broken wire
▪
10 kΩ: good state
▪
1 kΩ: pump start through actuation of limit switch
▪
< 300 Ω: short circuit
2)
Supplied assembled and pre-set. The electrical components can be connected and disconnected at the control cabinet via
plug-type connections.