6 Commissioning/Start-up/Shutdown
30 of 48
Hya-Duo D FL Compact
6.2 Operating limits
DANGER
Non-compliance with operating limits
Damage to the pump set!
▷
Comply with the operating data indicated in the data sheet.
▷
Avoid operation against a closed shut-off element.
▷
Never operate the pump set outside the limits specified below.
DANGER
Non-compliance with operating limits for the fluid handled
Explosion hazard!
▷
Never use the pump to handle different fluids which might react chemically
with each other.
▷
Never use the pump to handle a flammable fluid with a fluid temperature
above the ignition temperature.
6.2.1 Application limits
NOTE
On-site conditions deviating from the test conditions may have a negative impact
on the operating reliability. Regardless of the effective volume of the tank, the
operating reliability of the system must be checked in an on-site acceptance
inspection in accordance with DIN 14462.
The effective volume of the tank is selected to DIN 1988-500 as standard. Mains
water is refilled via a float valve.
To ensure a sufficient supply of fire-fighting water and when using a tank with
reduced effective volume observe the following application limits:
Table 7:
Application limits
Flow rate
Float switch
connection
Minimum inlet
pressure
3)
Maximum static
pressure
[m
3
/h]
[bar]
[bar]
≤ 18
G 1
1
/
4
1,5
8
≤ 36
G 2
1,5
8
≤ 48
G 2
3
8
3)
Minimum flow pressure at the float switch depending on the nominal flow rate