7 Operation
55 of 76
EtaLine Pro
1168.87/01-EN
7.4 Additional functions
7.4.1 Locking / unlocking the control panel
Operating modes and functions can only be selected when the control panel is
unlocked.
Table 28:
Locking / unlocking the control panel
Step 1: Activating the additional function setting mode
▪
Press and hold the control button (OK) for 10 seconds.
– The additional functions setting mode is active.
– The symbol flashes.
Step 2: Activating the setting mode
▪
Press the control button (OK).
▪
The current status of the control panel is shown.
Step 3: Locking / unlocking the control panel
▪
Select the desired status by changing the control element (+) or (-).
– H0 = control panel unlocked
– H1 = control panel locked
▪
Press the control button (OK) to confirm the status.
7.4.2 Test alert
Function
The test alert can be used to check the connection of the general fault message. The
test alert is indicated by alert 70 on the display, and the pump stops.
The test alert can be disabled by either disconnecting and re-connecting the power
supply or via the control element.