7 Operation
52 of 76
EtaLine Pro
1168.87/01-EN
100%
2 V
%
0%
10 V
1,5 V
U [V DC]
Fig. 32:
Analog 0 -10 V signal as setpoint input for the pump set
Setting the limits and parameters using the KSB ServiceTool for the following
functions:
▪
Starting up the pump
▪
Stopping the pump
Setting
Press the control button on the control element to activate the display from idle
mode. The display will show the current operating mode as well as, in alternation,
the electrical input power and the flow rate. If 5 minutes pass without any settings
being made or the control button being pressed, the display will revert to idle mode.
Table 24:
Starting and stopping 0 - 10 V
Step 1: Activating the functions (0 - 10 V)
▪
Press and hold the control button (OK) for 6 seconds.
– The functions setting mode is active.
Step 2: Selecting 0 - 10 V
▪
Set the desired function on the control element.
▪
The symbol will light up.
Step 3: Activating/deactivating 0 - 10 V
▪
Press the control button (OK).
– When the signal is activated, the circular segments will indicate the
value of the input signal.
NOTE
If 10 seconds pass without any settings being made or saved, the control unit will
revert to the previous settings.
NOTE
To start the pump the digital input 1 terminal pair must be bridged.
7.3.5 Bluetooth
Activating the Bluetooth function enables a connection to be established between
the pump set and the KSB Flow Manager app (smartphone) or the KSB ServiceTool
(PC).