5 Installation at Site
23 of 76
EtaLine Pro
1168.87/01-EN
NOTE
Do not install the pump at the lowest point of the system to prevent any impurities
from collecting in the pump.
CAUTION
Ingress of leakage into the motor
Damage to the pump!
▷
Never install the pump set with the "motor below".
The pump set may be flanged directly into the piping.
1. Position the pump set in the piping and fasten it.
2. Place a spirit level on the discharge nozzle to align the pump set.
5.4.1 Installation types
Horizontal installation
Fig. 7:
Horizontal installation of pump set, direction of flow from bottom to top
Fig. 8:
Horizontal installation, direction of flow from top to bottom
Turn the volute casing and/or pull-out unit by 180° so that the electronic system and
the control element remain in their current position on top and are easy to read.
Fig. 9:
Horizontal installation (for example under the ceiling)
Turn the volute casing and/or pull-out unit by 90° so that the frequency inverter
remains in its current position on top.