9 Related Documents
38
of
44
EA-C
9.4.4 Technical data of EA-C 200 to 250 (continuous-action and 24 V AC 3-point)
Table 17:
Technical data of EA-C 200 to 250 (continuous-action and 24 V AC 3-point)
Characteristic
EA-C 200
continuous-action
and 3-point
EA-C 200
continuous-
action
EA-C 200
continuous-
action
EA-C 250
continuous-action
and 3-point
EA-C 250
continuous-
action
EA-C 250
continuous-
action
Actuating force
[N]
20000
25000
Maximum positioning force
21)
[N]
10000
12500
Stroke
[mm]
95
Handwheel turns
[/10mm stroke]
50
Actuating speed
[mm/s]
0,2 - 0,4
Power supply
[V]
24 V AC/DC
230 V AC
320-575 V AC 3~
24 V AC/DC
230 V AC
320-575 V AC 3~
Frequency
[Hz]
50 (AC)
Nominal current
22)
[A]
4,2 (AC) / 2,6 (DC)
0,44
0,32
23)
4,6 (AC) / 2,9 (DC)
0,48
0,35
23)
Maximum current
22)
[A]
5,5 (AC) / 3,4 (DC)
0,57
0,42
23)
6 (AC) / 3,7 (DC)
0,62
0,42
23)
Maximum power input
24)
[W]
76 (AC) / 63 (DC)
81
85
23)
82 (AC) / 69 (DC)
88
91
23)
Duty cycle
25)
IEC 60034-1,8
S2 30 minutes, S4 50% operating time
26)
Enclosure
EN 60529
IP65
Allow. ambient temperature
[°C]
-20 to +60
Motor protection
Electronic motor current monitoring incl. safety tripping
Weight (without accessories)
[kg]
23
21)
Permissible average actuating force over the entire stroke range
22)
Values may be higher depending on accessories used.
23)
At 400 V 3-phase and 50 Hz
24)
For maximum actuating force; values may be higher depending on accessories used.
25)
At 25 °C ambient temperature
26)
Cycles per hour
Summary of Contents for EA-C