9 Related Documents
EA-C
35
of
44
9.4 Technical data
9.4.1 Technical data of EA-C 20 to 40 (continuous-action and 24 V AC 3-point)
Table 14:
Technical data of EA-C 20 to 40 (continuous-action and 24 V AC 3-point)
Characteristic
EA-C 20 continuous-action
EA-C 20 continuous-
action and 3-point
EA-C 40 continuous action
EA-C 40 continuous-action
and 3-point
Actuating force
[N]
2000
4000
Stroke
[mm]
50
Handwheel turns
[/10 mm
stroke]
12
Actuating speed
[mm/s]
0,45 - 0,9
Power supply
[V]
230 V AC 1~ 320 - 575 V AC 3~
24 V AC 1~
230 V AC 1~
320 - 575 V AC 3~
24 V AC 1~
Frequency
[Hz]
50
Nominal current
7)
[A]
0,07
0,08
8)
0,7 (AC) / 0,4 (DC)
0,11
0,11
8)
1,1 (AC) / 0,7 (DC)
Maximum current
7)
[A]
0,1
0,11
8)
0,9 (AC) / 0,6 (DC)
0,14
0,14
8)
1,4 (AC) / 0,9 (DC)
Maximum power input
9)
[W]
13
22
8)
12 (AC) / 11 (DC)
19
28
8)
18 (AC) / 16 (DC)
Duty cycle
10)
IEC 60034-1,8
S2 30 minutes, S4 50 % operating time - 1200 c/h
11)
Enclosure
EN 60529
IP65
Allow. ambient
temperature
[°C]
-20 to +60
Motor protection
Thermal monitoring and overload protection
Weight (without
accessories)
[kg]
8
7)
Values may be higher depending on accessories used.
8)
At 400 V 3-phase and 50 Hz
9)
At maximum actuating force; Values may be higher depending on accessories used.
10)
At 25 °C ambient temperature
11)
Cycles per hour
Summary of Contents for EA-C
Page 43: ......