FCU 500, FCU 505 · Edition 02.17
71
Fault signalling
Fault message (blinking)
DISPLAY
Description
Fuse defective
51
Device fuse F1 is defective
Permanent remote reset
52
Remote reset input activated > 25 s
STL overtemperature
60
The safety temperature limiter (STL) has detected an overtemperature
condition.
Thermocouple 1 cable discontinuity
62
Thermocouple 1 (terminals 5 and 6) defective
Thermocouple 2 cable discontinuity
63
Thermocouple 2 (terminals 7 and 8) defective
Thermocouple 1 short-circuit
64
Sensor short-circuit in thermocouple 1
Thermocouple 2 short-circuit
65
Sensor short-circuit in thermocouple 2
Temperature difference limit value
66
Set temperature difference between thermocouples exceeded
(parameter 23)
Furnace temperature outside range
67
Operation outside temperature range
Burner control unit operating signal
70
No operating signal within the period defined in parameter 47
Burner control units not ready
72
Burner control units do not signal Standby mode
Internal error
89
Error in processing internal data
Temperature monitoring
90
Internal fault in module
Internal error
94
Error at digital inputs
Internal error
95
Error at digital outputs
Internal error
96
Error when checking the SFR
Internal error
97
Error when reading the EEProm
Internal error
98
Error when writing to the EEProm
emBoss
99
Shut-down without application error
Minimum capacity not reached
A
Closed position not reached after 250 s
Maximum capacity not reached
A
Purge position not reached after 250 s
Ignition capacity not reached
A
Ignition position not reached after 250 s
Communication with bus module (display bE)
E
Internal communication with bus module has suffered a fault
▼