FCU 500, FCU 505 · Edition 02.17
66
Fieldbus communication via Ethernet
PLC output information (FCU
➔
PLC)
This module/register transfers information on signals
which the PLC uses to control the FCU back to the PLC.
This allows the signal transfer from the PLC to the FCU
to be checked.
Bit Byte n
Format
0
Reset
BOOL
1
Start
BOOL
2
Controlled air flow
BOOL
3
Operating signal
BOOL
4
Free
BOOL
5
Free
BOOL
6
Open control element, three-point step Open
1)
BOOL
7
Close control element, three-point step Close
1)
BOOL
1)
Only with three-point step control via bus.
FCU input terminal information
(FCU
➔
PLC)
This module/register transfers the signal states of the
digital inputs on the FCU (input terminals) to the PLC.
Bit Byte n
Byte n+1
Byte n+2
Format
0
Terminal 1
Terminal 48
Terminal 68
BOOL
1
Terminal 2
Terminal 49
Free
BOOL
2
Terminal 3
Terminal 50
Free
BOOL
3
Terminal 4
Terminal 51
Free
BOOL
4
Terminal 44
Terminal 52
Free
BOOL
5
Terminal 45
Terminal 65
Free
BOOL
6
Terminal 46
Terminal 66
Free
BOOL
7
Terminal 47
Terminal 67
Free
BOOL
FCU output terminal information (FCU
➔
PLC)
This module/register transfers the signal states of
the digital outputs on the FCU (output terminals) to
the PLC.
Bit Byte n
Byte n+1
Format
0
Terminal 13
Terminal 53
BOOL
1
Terminal 14
Terminal 54
BOOL
2
Terminal 15
Terminal 55
BOOL
3
Terminal 16
Terminal 56
BOOL
4
Terminal 17
Terminal 57
BOOL
5
Terminal 18
Terminal 58
BOOL
6
Terminal 41
1)
Free
BOOL
7
Terminal 42
Free
BOOL
1)
Only for FCU..F2: terminal 53 is used as an input.
Bit 6 has no function.
▼