FCU 500, FCU 505 · Edition 02.17
99
Parameters
FCU
Frequency converter
Contact between terminals
Signal to
Position
Fan speed
53
55
DI 2/DI 3
Ignition
Minimum/Ignition capacity
53
56
DI 3
0 – 20 mA
Any speed between minimum and maximum capacity
53
54
DI 1/DI 3
Purge
Maximum capacity
Manual mode
In Manual mode, the frequency converter can be set
to the speed for maximum air volume or minimum air
volume (pilot air volume). Adjustment by the control
system is not possible. No timeout is active when accel-
erating to these speeds.