background image

 SAFETY INSTRUCTIONS 

1

3

OPTISWIRL 5080

www.krohne.com

07/2020 - 4008054001 - AD OPTISW5080 Exd Gb-Db en R01

1.1  General notes

These additional instructions apply to flameproof versions of vortex flowmeters with following 
specifications:

ATEX category:
II 2/1 (1) G and II 2D for compact version and remote signal converter
II 1G and II 2D for remote flow sensor

Equipment protection level (EPL):
Gb and Db for compact version and remote signal converter; Ga and Db for remote flow 
sensor

Ex marking compact version: Ex db [ia Ga] ia IIC T4 Gb and Ex tb IIIC T85

°

C Db

Ex marking remote signal converter: Ex db [ia Ga] IIC T4 Gb and Ex tb IIIC T85

°

C Db

Ex marking remote flow sensor: Ex ia IIC T4 Ga and Ex tb IIIC T103

°

C Db

They complete the standard documentation for the non explosion-protection versions.

The information given in this instruction contains only the data relevant to explosion protection.
The technical details given in the manual for the non explosion-protected versions remain 
unchanged unless they will be excluded or replaced by this instruction.

1.2  EU conformity

The manufacturer declares with the EU declaration of conformity on his own responsibility 
conformity with the protection goals of directive 2014/34/EU for use in hazardous areas with gas 
and dust.

Conformity with harmonised standards was checked by a Notified Body in accordance with 
EN 60079-0:2012, EN 60079-1:2014, EN 60079-11:2012, EN 60079-26:2007 and
EN 60079-31:2014.
The EU declaration of conformity for the equipment categories is based on the EU type 
examination certificate:

The "X" after the certificate number refers to special conditions for safe use of the device, which 
have been listed in these instructions.
If needed the EU type examination certificate can be downloaded from the manufacturer's 
website.

Sira 19ATEX2001 X

Sira 19ATEX2001 X

Sira 19ATEX2001 X

Sira 19ATEX2001 X

Summary of Contents for OPTISWIRL 5080

Page 1: ...2 D Equipment protection level Equipment protection level Equipment protection level Equipment protection level Ga Gb and Db OPTISWIRL 5080 OPTISWIRL 5080 OPTISWIRL 5080 OPTISWIRL 5080 Supplementary...

Page 2: ...evice description 5 2 2 Marking 5 2 3 Safety specifications 7 2 4 Flammable products 7 2 5 Ambient temperature temperature classes 8 2 6 Electrical data 10 3 Installation 11 3 1 Mounting 11 3 2 Specia...

Page 3: ...tion contains only the data relevant to explosion protection The technical details given in the manual for the non explosion protected versions remain unchanged unless they will be excluded or replace...

Page 4: ...vice which have been listed in these instructions If needed the IEC certificate can be downloaded from the manufacturer s website 1 4 Safety instructions If these instructions are not followed there i...

Page 5: ...2 1 Example of a nameplate for the compact version 1 Model number and serial number 2 Marking according to the notified body 3 Note for disposal 4 Manufacturer logo 5 IP rating for enclosure 6 Manufa...

Page 6: ...intrinsic safety Do not open when energized Failure to follow these instructions can result in death or serious injury 47058 DUISBURG GERMANY ST S N ORIGIN SUPPLY MWP 100 F 38 C MAX AMB TEMP 176 F 80...

Page 7: ...on level EPL remote flow sensor Ga Ex marking remote flow sensor Ex ia IIC T4 Ga Equipment protection by flameproof enclosure Equipment protection by flameproof enclosure Equipment protection by flame...

Page 8: ...mbient temperature range Insulation must be limited to the piping Unobstructed ventilation of the signal converter and the remote flow sensor connection box must be ensured Temperature class Permissib...

Page 9: ...e operator has to ensure the temperature limit by temperature measurements at the housing reference point For high temperature applications positioning the electronics housing to the side or bottom an...

Page 10: ...must be disconnected to shorten the cable run the cable through conduit or for some other reason you must disconnect the cable at the sensor junction box end You cannot disconnect the cable at the si...

Page 11: ...is clearly visible it can be operated from a location with secure footing Important notes for mounting Important notes for mounting Important notes for mounting Important notes for mounting Ensure ar...

Page 12: ...s with a tensile strength of at least 240 N mm Devices marked as category 1 G or EPL Ga Devices marked as category 1 G or EPL Ga Devices marked as category 1 G or EPL Ga Devices marked as category 1 G...

Page 13: ...screwed in it must form a flameproof joint with the housing with a minimum thread length of 8 mm A suitable mechanical stopping box must be provided in accordance with installation requirements The c...

Page 14: ...round test voltage 500 VAC or 707 VDC between terminal and earth ground terminal 4 4 Grounding Equipotential bonding Vortex flowmeter must be connected to the equipotential bonding system of the hazar...

Page 15: ...y only be operated if the equipment parts necessary for safety are effective in the long run and are not rendered inoperable during operation In case of operation with flammable products the measuring...

Page 16: ...llation is within the responsibility of the operator Due to the modular design of the vortex flowmeters from a safety perspective the electrical equipment built into the signal converter can be replac...

Page 17: ...erve the information above Also ensure that all process connections and the pipeline are depressurised and free of product Where environmentally critical products are concerned carefully decontaminate...

Page 18: ...7 NOTES 18 OPTISWIRL 5080 www krohne com 07 2020 4008054001 AD OPTISW5080 Exd Gb Db en R01...

Page 19: ...NOTES 7 19 OPTISWIRL 5080 www krohne com 07 2020 4008054001 AD OPTISW5080 Exd Gb Db en R01...

Page 20: ...ces Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 203 301 0 Fax 49 203 301 10389 info krohne com KROHNE 07 2020 4008054001 AD OPTISW5080 Exd Gb Db en R01 Subjec...

Reviews: