background image

11

Block Number

Standard-Configuration
(function block output value)

PA039742. GSD
Ident-No. 9742

Default
unit:

1

Mass Flow

AI-FB

kg/s

2

Density

AI-FB

kg/m3

3

Medium Temperature

AI-FB

K

4

Mass Totaliser

Totaliser-FB

kg

All other values of ModeTot are not allowed. Value is ignored; totaliser remains in its last valid
setting.

The standard block configuration may be changed by the customer but using the default set-
tings is highly recommended. If the standard block configuration should be changed by the
customer an acyclic master tool must be used to change the “channel parameter” value of the
block which should be connected to another transducer output value.

2

2..4

4..2

2  P

Prro

offiille

e  s

sp

pe

ec

ciiffiic

c  G

GS

SD

D  ffiille

e::  P

PA

A0

03

39

97

74

42

2..  G

GS

SD

D

The functionality of the profile specific GSD file is limited. This GSD file includes only four
blocks:

S

Se

ettT

To

ott::

SetTot =0:

Totaliser is totalising. 

SetTot =1:

Totaliser will be reset to 0 and stays at 0 until SetTot is switched back again
to 0. If the value of SetTot changes from “1”  to “0” the totaliser starts count-
ing from 0.

SetTot =2:

Totaliser is set to the value defined by PresetTot. PresetTot can be written via
a acyclic master (totaliser in block 4 = Slot 4 Index 32; totaliser in block 5 =
Slot 5 Index 32; totaliser in block 6 = Slot 6 Index 32). If the value of SetTot
changes from “2”  to “0” the totaliser starts counting from the current value
defined by PresetTot.

SetTot ? 2:

not allowed. Value is ignored; totaliser remains in its last valid setting.

M

Mo

od

de

eT

To

ott::

ModeTot = 0

totaliser totalises positive and negative values.

ModeTot = 1

totalises only positive values.

ModeTot = 2

totalises only negative values.

ModeTot = 3

totaliser is stopped, no totalization will be done.

ModeTot = 248 totalises all values as positive (negative values will be multiplied with “-1.0”)

ModeTot = 249 totalises all values as negative (positive  values will be multiplied with “-1.0”)

The device has to be switched from “Manufacturer Specific” (full functionality) to “Profile
Specific” (interchangeable basic configuration) by using a master class 2 tool (IDENT_NUM-
BER_SELECTOR: Slot 0, Index 40 change byte value to 0). After this the device has to be pro-
jected by using the PA039742.GSD file.

2

2..4

4..3

3  C

Cyyc

clliic

c  d

da

atta

a  e

ex

xc

ch

ha

an

ng

ge

e

During network configuration the user has to define which function block outputs of the
MFC300 PROFIBUS RS-485 should be transferred cyclically to the master. Network configura-
tion will be done using one of the GSD files described above. The order of transmission of a
function block always remains the same even if a function block is defined as an “Empty” block
(in this case, no function block output data will be sent to the master and all function block out-
puts following the “Empty” block will move up one position)

.

Summary of Contents for OPTIMASS MFC 300

Page 1: ...FC C 3 30 00 0 P PR RO OF FI IB BU US S D DP P R RS S4 48 85 5 d de ev vi ic ce e w wi it th h P PA A p pr ro of fi il le e M MF FC C 3 30 00 0 P PR RO OF FI IB BU US S P PA A M MB BP P d de ev vi ic...

Page 2: ...2...

Page 3: ...Structure of Function Block Output Values 12 2 7 Diagnosis 13 2 8 Display Parameters PROFIBUS 14 2 9 Technical Data 21 3 PROFIBUS PA DEVICE MBP INTERFACE PA PROFILE 3 01 3 1 Software History 22 3 2 PR...

Page 4: ...ym mb bo ol ls s U Us se ed d The follwing is a guide to the meaning of the symbols used in this handbook The symbols fall into two types The rectangular symbols with blue background draws the reader...

Page 5: ...y Responsibility for suitability and intended use of this device rests solely with the user Improper installation and operation of the device may lead to loss of warranty In addition the Terms and Con...

Page 6: ...ait approx 10 seconds before you switch off the MFC300 after you have done both a parameter download via PROFIBUS or a manual change of a parameter value via the local display Please wait approx 15 se...

Page 7: ...thers HW Config others GSD Manufacturer specif ic for standard DP PA segment cou pler KR014510 GSD MFC300 RS 485 Rev 1 GSD Profile specific for standard DP PA seg ment coupler PA039742 GSD Flow dens t...

Page 8: ...B B D C D C I I I I 5V R2 R1 R1 I 110nH R1 390 R2 220 3 B B D C D C I I I I 5V R2 R1 R1 I 110nH R1 390 R2 220 2 1 External connection PROFIBUS DP device at low datarates connected with spur Spurs are...

Page 9: ...data exchange of the coriolis mass flow meter MFC300 The application of the manufacturer independent Ident No 9742hex GSD file PA039742 GSD provides interchangeability of devices i e an exchange of co...

Page 10: ...ings to select the units for local display and PROFIBUS Modifications of the units of the display will have no effect on the data transferred via PROFIBUS A master class 2 tool is required to modify t...

Page 11: ...6 Slot 6 Index 32 If the value of SetTot changes from 2 to 0 the totaliser starts counting from the current value defined by PresetTot SetTot 2 not allowed Value is ignored totaliser remains in its la...

Page 12: ...ven in the following tables 2 5 Profiles The MFC300 PROFIBUS RS 485 Interface supports the PROFIBUS PA Profile Version 3 01 The MFC300 PROFIBUS RS 485 Interface with PA Profile 3 01 supports the follo...

Page 13: ...to get the quality information of the measurement value G Go oo od d n no on n C Ca as sc ca ad de e function block output value is ok and can be used without restrictions G Go oo od d C Ca as sc ca a...

Page 14: ...ser 3 where fitted for PROFIBUS Devices the counter can be reset to zero in this menu step 1 reset counter N No o exits the function without reset Y Ye es s resets the counter and exits the func tion...

Page 15: ...l be set in the long status information bytes of the PROFIBUS interface if the actual value of the totaliser is outside these limits This can be also used as a status output choosing the function pres...

Page 16: ...y voltage for the PROFIBUS C5 y 2 Time Constant Time constant for this function block C5 y 3 Error Behaviour Defines the behaviour of this function block in case of errors Hold Value last valid OUT va...

Page 17: ...blocks Only PROFIBUS values can be selected here The analogue inputs are shown with exactly the value as seen on the PROFIBUS C6 4 1 Measurement 1 line FB1 Analog inp 1 FB2 Analog inp 2 FB3 Analog inp...

Page 18: ...6 3 Load Settings in this menu all settings can be loaded from different storage places where settings have been saved before step 1 Load Settings break Exits the menu without loading factory setting...

Page 19: ...tion Y Ye es s quick access activated N No o quick access not activated C6 9 3 reset totaliser 3 The reset can be activated in the Quick Setup to get a quick access of the function Y Ye es s quick acc...

Page 20: ...orted no extras D2 2 5 PB Cold Start Reset N No o terminates the function Y Ye es s PROFIBUS cold start will be carried out at once The programming mode is terminat ed N No ot te e During a PROFIBUS c...

Page 21: ...profile PA Profile compact class B V3 01 Address range 0 126 default 126 0 to 125 via set_slave_add 0 to 126 via Local Display 126 via FACTORY_RESET 2712 Local control local display and operator inter...

Page 22: ...ibus PA Device V2 2 1 061117 Simatic PCS7 Others HW Config Others GSD Manufacturer specific for standard DP PA segment coupler KR014511 GSD MFC300 MBP Rev 1 GSD Manufacturer specific for segment coupl...

Page 23: ...In Out 3 Alternative wiring because the current linkage between the device and the PROFIBUS PA cable is not polarised N No ot te e Although the PROFIBUS MBP technology supports power supply via the P...

Page 24: ...elongs to the KR014511 GSD YP014511 GSD and includes the com plete functionality concerning the cyclic data exchange of the coriolis mass flow meter MFC300 The application of the manufacturer independ...

Page 25: ...the units for local display and PROFIBUS Modifications of the units of the display will have no effect on the data transferred via PROFIBUS A master class 2 tool is required to modify the units for PR...

Page 26: ...rer Specific full functionality to Profile Specific interchangeable basic configuration by using a master class 2 tool IDENT_NUM BER_SELECTOR Slot 0 Index 40 change byte value to 0 After this the devi...

Page 27: ...r coriolis mass flow devices This block provides the parameters and functions defined in PA Profile 3 01 Eight Analog Input AI function blocks as default Mass Flow Density Medium Temperature Volume Fl...

Page 28: ...to get the quality information of the measurement value G Go oo od d n no on n C Ca as sc ca ad de e function block output value is ok and can be used without restrictions G Go oo od d C Ca as sc ca a...

Page 29: ...B6 Totaliser 3 for PROFIBUS Devices the counter can be reset to zero in this menu step 1 reset counter N No o exits the function without reset Y Ye es s resets the counter and exits the func tion A4 S...

Page 30: ...l be set in the long status information bytes of the PROFIBUS interface if the actual value of the totaliser is outside these limits This can be also used as a status output choosing the function pres...

Page 31: ...y voltage for the PROFIBUS C5 y 2 Time Constant Time constant for this function block C5 y 3 Error Behaviour Defines the behaviour of this function block in case of errors Hold Value last valid OUT va...

Page 32: ...blocks Only PROFIBUS values can be selected here The analogue inputs are shown with exactly the value as seen on the PROFIBUS C6 4 1 Measurement 1 line FB1 Analog inp 1 FB2 Analog inp 2 FB3 Analog inp...

Page 33: ...6 3 Load Settings in this menu all settings can be loaded from different storage places where settings have been saved before step 1 Load Settings break Exits the menu without loading factory setting...

Page 34: ...tion Y Ye es s quick access activated N No o quick access not activated C6 9 3 reset totaliser 3 The reset can be activated in the Quick Setup to get a quick access of the function Y Ye es s quick acc...

Page 35: ...pported no extras D2 2 5 PB Cold Start Reset N No o terminates the function Y Ye es s PROFIBUS cold start will be carried out at once The programming mode is terminat ed N No ot te e During a PROFIBUS...

Page 36: ...e_add 0 to 126 via Local Display 126 via FACTORY_RESET 2712 FDE yes separate fault discon nection electronics provided Local control local display and operator interface at device Fault current 6 mA f...

Page 37: ...37...

Page 38: ...38...

Page 39: ...39...

Page 40: ...snl net Iran KROHNE Liaison Office North Sohrevardi Ave 26 Sarmad St Apt 9 Tehran 15539 TEL 98 21 874 5973 FAX 98 21 850 1268 e mail krohne krohneiran com Italy KROHNE Italia Srl Via V Monti 75 I 2014...

Reviews: