9 Connection
9.3 Connecting the pump station to the power supply
ATTENTION
Damage to device through impurity in the pipe system.
► During welding work attach protective covers in front of the connecting flanges.
► Ensure when welding that welding beads and abrasive dust cannot get into the pipe system and
the pump station.
► Ensure that a commissioning filter is installed when the pipe system is flushed and cleaned using
the pump.
ATTENTION
Damage to device through mechanical stress.
► Ensure that the pump station is mounted free of mechanical stresses in the pipe system.
► Observe the tightening torques.
1.
Attach protective covers in front of the connecting flanges before welding work.
2.
Avoid mechanical tensions in the pipe system when carrying out connecting.
3.
Place the piping in position and support the weight of the piping. Do not use the pump station as
a support for connected piping.
4.
Install compensating elements if temperature-related material expansion is possible.
5.
Check the linear, height and angular offset and correct if necessary.
ð
If the screws tighten easily, this is a sure sign that the installation is stress-free.
6.
Tighten the connecting screws with torque,
Ä
7.
Lay the suction line hermetically sealed with a slight ascending slope.
9.3 Connecting the pump station to the power supply
Personnel qualification:
o
Electrician
Personal protective equipment:
o
Work clothing
o
Protective gloves
o
Safety boots
DANGER
Risk of death resulting from electric shock.
► Ensure that the electrical power supply is de-energized and is secured against being switched
back on.
► Before commissioning ensure correct grounding and equipotential bonding.
► Observe the operating instructions of the electrical components.
1.
Carefully earth the base frames with the screwing.
2.
Connect the electrical components of the pump station in accordance with the corresponding op-
erating instructions.
3.
When connecting the pump station to the complete system continue equipotential bonding.
Operating instructions
OID 06en-GB Edition 2019-11
19