67
8.11.4 Hard generation limit control
Users can set the output power of the inverter through THE LCD (Hard generation limit control);
The operation steps are as follows:
Step 1: Press the "Enter" button in the main interface to ENTER the interface below, select the
"Settings" option through the "Up" button and the "Down" button, and then press the
"Enter" button to ENTER the next level menu.
Step 2: After entering the following menu, select the option of "Power regulation setting" through
the "Up" and "Down" buttons, and then press the "Enter" button to Enter the next menu.
Step 3: After entering the following menu, enter the password through the "Up" button and "Down"
button to enter the next menu. Power management information is an important parameter,
in order to ensure the safety of users and set, password can be obtained by consulting
customer service.
Step 4: After entering the password correctly, the user can access the following menu. You can
use up or down keys to select "Hard Limit Control" and press ENTER. Press the up or
down key to select "Generation Limit Control " to limit the power output. After the
Settings are complete, OK is displayed. Press Esc to return to the home screen. The
reference steps are shown below:
Summary of Contents for KY-EST06KH
Page 1: ...1 User Manual 3 Phase Hybrid Inverter KY EST06KH KY EST20KH V1 0...
Page 10: ...10 Dimensions KY EST06 10KH unit mm Dimensions KY EST12 20KH unit mm...
Page 12: ...12 Fig1 5 Three phase Meter Dimension unit mm...
Page 15: ...15 Each successive press of the button selects a new parameter...
Page 16: ...16 Each successive press of the button selects a new parameter...
Page 17: ...17 Each successive press of the button selects a new parameter...
Page 32: ...32 View the power quality response mode...
Page 34: ...34 Figure 5 2 2...
Page 68: ...68...
Page 70: ...70 Figure...