8. Operation

Use Decrease value to set decrease in temperature for all time intervals. The 
nighttime setback can be defined individually for every day of the week in 
Schedule. Press a button to set the temperature setpoint reduction for a specific 
time interval. Time intervals for 24 hours are set every 30 minutes.

TIME INTERVAL IS OMITTED WHEN DECREASE VALUE IS SET TO 0, 
EVEN IF THE TIME RANGE IS SET.

8.22 Fuel level configuration

The controller uses fuel level sensor to monitor fuel level.
Set 

Fuel level

 

sensor

 to 

Enabled

 in:

Service settings > Burner settings > Storage bin settings

When the fuel level is below the fuel level sensor, the controller will display the 
following message:
„Low fuel level” and will continue feeding the fuel until the minimum fuel level 
is reached. In fuel reserve mode, the remaining fuel (in kilograms) is displayed 
in the main screen. If no fuel is added by the user, and the reserve is used, the 
controller with shutdown the burner before the feeder is completely emptied. 
Set 

Fuel level sensor

 to 

Disabled 

to disable the fuel level sensor. Fuel level 

will be monitored as described below. The controller features a second fuel 
level control system, which indicates current fuel level at all times. The level is 
determined based on the feeder output, storage bin capacity or based on the 
storage bin calibration. The control system can be disabled by setting the alarm 
level to OFF. 

Boiler settings > Fuel level > Alarm level

Tip: fuel level can also be checked on the ecoSTER TOUCH room temperature 
controller.
• 

Fuel level indicator: Every time the fuel is added to the storage tank, press 
and hold current fuel level value, the following message is displayed: 
 
 
 
 
 
 
 
 
 
 
 
 
 
’’”Set fuel level to 100%”. Press YES to set fuel level to 100%.  
Note: The fuel can be added anytime, i.e. there is no need to wait for  
the fuel storage tank to be completely emptied. The fuel must be added to 
100% level and the level set to 100% as described. 

• 

Operation: The controller determines fuel level based on its consumption. 
The factory settings will not always reflect the actual fuel consumption, 
and thus fuel level calibration may be required. No additional fuel level 
sensors are required.

• 

Calibration: Add the fuel to the storage tank to the level corresponding to 
its 100% capacity and set the following parameter:

 

Boiler settings > Fuel level > Fuel level calibration >  
Fuel level 100% 

The fuel level indicator in the main window is set to 100%.  
The calibration process is indicated by a blinking fuel level indicator. The 
indicator blinks until the point corresponding to the minimum fuel level is 
set. Check fuel level in the storage bin regularly. When minimum level is 
reached, set the following parameter: 

Boiler settings > Fuel level > Fuel level calibration >  
Fuel level 0% 

Calibration is not required, if Feeder output and Storage bin volume are 
set in: 

Service settings > Burner settings > Operation

8.23 Info

Info menu allows to view measured temperature and all installed devices.

IF THE MIXING VALVE EXTENSION MODULE IS INSTALLED, 
ADDITIONAL INFO SCREENS ARE AVAILABLE. „CAL” MESSAGE IN THE 
INFO SCREEN BY THE VALVE POSITION INDICATES CALIBRATION.
IN PROGRESS. WAIT UNTIL THE MIXING VALVE ACTUATOR 
CALIBRATION IS FINISHED (CURRENT STATUS IS DISPLAYED).

8.24 Manual control

The controller allows to disable the devices, i.e. pump, feeder motor or fan 
manually to check device functions and wiring.

MANUAL CONTROL MENU CAN BE ACCESSED IN STAND-BY MODE 
ONLY, I.E. WITH BOILER SHUTDOWN.

PROLONGED OPERATION OF THE FAN, FEEDER OR OTHER DEVICE 
MAY RESULT IN A HAZARD.

Summary of Contents for Platinum Bio ecoMAX860P3-O TOUCH (VG)

Page 1: ...Platinum Bio ecoMAX860P3 OTOUCH VG USER MANUAL RU EN...

Page 2: ......

Page 3: ...RU EN USER MANUAL 5 49...

Page 4: ......

Page 5: ...Platinum Bio ecoMAX860P3 OTOUCH VG R U...

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ...Platinum Bio ecoMAX860P3 OTOUCH VG...

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ...5...

Page 36: ......

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ......

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ......

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ......

Page 49: ...Leader in pellet boilers Platinum Bio ecoMAX860P3 O TOUCH VG controller User Manual E N G L I S H E N...

Page 50: ...50 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers...

Page 51: ...choosing KOSTRZEWA equipment top quality device manufactured by a renowned and highly valued company both in Poland and abroad The KOSTRZEWA company was established in 1978 From the very beginning the...

Page 52: ...52 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers...

Page 53: ...4 4 Storing documents 54 5 Symbols and designations 54 6 WEEE Directive 2002 96 WE 54 7 User menu 55 8 Operation 57 9 Alarm description 63 Platinum Bio ecoMAX 860P controller Service manual 65 10 Hydr...

Page 54: ...out of reach of children 2 General The controller is a device for controlling an operation of a boiler with an automatic solid fuel feeder and an igniter The flame is detected by an optical flame brig...

Page 55: ...temperature sensor CH sensor Continuous pump Boiler settings Boiler temperature setpoint Boiler outdoor temperature compensation Boiler heating curve Curve translation Room temperature coefficient Po...

Page 56: ...ings 2 3 Mixing valve temperature setpoint Mixing valve room thermostat Mixing valve outdoor temperature compensation Mixing valve heating curve Curve translation Room temperature coefficient Mixing v...

Page 57: ...perature weather compensation 9 values affecting temperature setpoint room thermostat contacts open room temperature setpoint not reached temperature setpoint decreased by active intervals boiler temp...

Page 58: ...vice settings Burner settings Operation Feeder operation time is determined automatically based on the required current burner power feeder output and fuel calorific value OPERATION mode parameters ca...

Page 59: ...leaning settings Burner cleaning settings can be modified in Boiler settings Cleaning Continuous burner operation time after which it is automatically shut down cleaned and started again is set in Bur...

Page 60: ...k hysteresis DHW pump is activated to charge the DHW storage tank AT LOW HYSTERESIS SETTING DHW PUMPWILL ACTIVATE QUICKER AFTERTHE DHWTEMPERATURE DECREASES 8 17 DHW circulation The settings can be mod...

Page 61: ...too high room temperature may fluctuate 8 20 Outdoor temperature compensation Depending on the measured outdoor temperature both the boiler temperature setpoint and the mixing valve circuit temperatur...

Page 62: ...rrent fuel level value the following message is displayed Set fuel level to 100 PressYES to set fuel level to 100 Note The fuel can be added anytime i e there is no need to wait for the fuel storage t...

Page 63: ...ith room temperature controller The controllers are compatible with ecoSTERTOUCH room temperature controller with room thermostat function The room temperature controller provides useful information f...

Page 64: ...ected to the electronics via a digital communication link RS485 If cable is damaged Caution No communication alarm is displayed The controller continues operation with programmed parameters Check repl...

Page 65: ...Leader in pellet boilers Platinum Bio ecoMAX860P3 O TOUCH VG controller SERVICE manual E N G L I S H E N...

Page 66: ...valve circuit pump 8 CT4 mixing valve circuit temperature sensor 9 DHW storage tank 10 DHW pump 11 temperature sensor CT4 DHW 12 CT6 P weather compensator 13 ecoSTERTOUCH room temperature controller w...

Page 67: ...1 settings Select mixing valve 1 thermostat ecoSTERT1 menu service settings mixing valve 1 settings Diagram with two controlled heating circuits and DHW storage tank 10 Hydraulic diagrams 1 boiler 2...

Page 68: ...ng valve 2 heating curve 0 3 0 8 menu mixing valve 2 settings Mixing valve 2 outdoor temperature compensation ON menu mixing valve 2 settings Select mixing valve 2 thermostat ecoSTERT1 menu service se...

Page 69: ...ture compensation ON menu mixing valve 1 settings Select mixing valve 1 thermostat ecoSTERT1 menu service settings mixing valve 1 settings Mixing valve 2 control Floor heating ON menu service settings...

Page 70: ...in and sunlight Storage and transport temperature must not exceed 15 65 C Do not expose to vibrations above those occurring in standard vehicle traffic conditions 13 Installing controller 13 1 Environ...

Page 71: ...g terminals Standard enclosure may be used User has access to the module front panel only The module can also be installed in the boiler components enclosing the entire module The enclosure does not p...

Page 72: ...als 1 21 are used for connecting devices which require 230V mains supplyTerminals22 49areusedforconnectinglowvoltagedevices upto12V CONNECTION CABLES MUST NOT CONTACT ANY SURFACESWITH TEMPERATURE HIGH...

Page 73: ...module variant O module B GRATE ACTUATOR MALE CONNECTOR GREEN MALE CONNECTOR TURQUOISE MALE CONNECTOR BLUE BLUE ORANGE SYSTEM ENCLOSURE BURNER TEMP BLOWER GEAR MOTOR HEATER TERMINAL BLOCK FEMALE CONNE...

Page 74: ...74 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers 13 Installing controller Wiring diagram for ecoMAX860P3 OTOUCH VG controller...

Page 75: ...75 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers 13 Installing controller Wiring diagram auxiliary module B to ecoMAX860P3 OTOUCH VG controller...

Page 76: ...auxiliary boiler control alarm signaling or DHW circulation pump control AC ash removal motor HWP DHW circulation pump BC cleaning motor PM C CH pump circuit C GC grate actuator SM C CH mixing valve c...

Page 77: ...ters above the ground at least 1 5 m from windows chimneys and other heat sources which may affect temperature measurements Use min 0 5 mm2 cables with length up to 25 m Cable polarity is not relevant...

Page 78: ...nstaller in accordance with the boiler documentation The auxiliary boiler should be connected via a relay to the terminals 46 47 Example wiring diagram 1 controller 2 auxiliary boiler gas or oil 3 rel...

Page 79: ...lve circuit temperature is minimum corresponds to 0 OFF position of the controller Note the position for verification purposes disconnect the controller power supply connect the mixing valve actuator...

Page 80: ...alorificvalue Operationwithoxygensensor ON OFF Cleaning Max linearactuatoroperationtime Linearactuatorextended Linearactuatorretracted Ashremovaltime OFF Heatexchangercleaningtime OFF Variable grate g...

Page 81: ...ffer tank control Charging start temperature Charging end temperature Heating system start Mixing valve 1 5 settings 1 Mixing valve control Select thermostat Mixing valve minimum temperature Maximum m...

Page 82: ...s if the boiler temperature is reduced below the boiler temperature setpoint by the boiler hysteresis the burner is started automatically Cycle time in OPERATION mode Fuel feeding cycle time in OPERAT...

Page 83: ...not use this parameter after fuel level calibration Fuel level sensor Enabling the fuel level sensor means that after low fuel level is detected the controller will automatically shutdown after burni...

Page 84: ...ted It protects the boiler against condensation due to the cooling with cold water returning from the system Note deactivating the boiler pump does not guarantee boiler protection against condensation...

Page 85: ...ode or DHW priority mode NO boiler pump works normally 15 4 Buffer tank Buffer tank setting Buffer tank control Activates operation mode with buffer tank Charging start temperature Charging start temp...

Page 86: ...ration time constant The higher the value the slower the actuator response to temperature deviation If the value is too low it may cau se unnecessary actuator movement if the value is too high it will...

Page 87: ...re is below 5 C the boiler pump is activated to force circulation of the boiler water If the temperature does not increase the burner is activated THIS FUNCTION MAY NOT BETHE SOLE PROTECTION AGAINST F...

Page 88: ...earactuatorretracted Ashremovaltime OFF Heatexchangercleaningtime OFF Variable grate geometry Control Actuatoratnominalpower Actuatoratminimumpower Linearactuatordelay Actuatorstrokeatreturn Burnerstr...

Page 89: ...tings Buffer tank control Charging start temperature Charging end temperature Heating system start Mixing valve settings 1 Mixing valve control Select thermostat Mixing valve minimum temperature Maxim...

Page 90: ...pump nighttime setback Mixing valve settings 1 Mixing valve temperature setpoint Mixing valve room thermostat Mixing valve outdoor temperature compensation Mixing valve heating curve Curve translation...

Page 91: ...91 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers Notes...

Page 92: ...92 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers Notes...

Page 93: ...93 Platinum Bio ecoMAX 860P User Manual EN 03 17 Leader in pellet boilers...

Page 94: ......

Reviews: