Air can be extracted from room in which the device is mounted, another room or
from outside of the building. Air can be extracted from room in which the device is
mounted, another room or from outside of the building. Install air filter of filtration
class G3 at the inlet channel.
In order to achieve optimal device parameters, provide air flow of 300m
3
/h. To minimize
losses associated with air resistance, cables must be performed in a straight line.
For DN200 the total length of the air inlet and outlet should not exceed 10m.
air outlet
air inlet
Air cables connection