After selecting the Ping Failure event type, the system will change the Relay
Output to “short” state, light the alarm LED and continuously ping the target
device. When the ping failure for Reset Time times out, the system will change
the Relay Output to “open” state and turn off the alarm LED for the amount of
time entered in Hold Time. After the Hold Time times out, the system will start
sending ping commands to the remote device.
For example, the Reset Time is set to 10 sec and the Hold Time is set to 40 sec.
The system will turn the Relay Output and Alarm LED off after ping has failed for
10 seconds (Reset Time). The system will turn the Relay Output and alarm LED
on again after 40 seconds (Hold Time).
The change of state of a Relay Output Ping Failure Event, see the chart below.
Super Ring Failure
Select Super Ring Failure. When the Rapid Super Ring topology is changed, the
system will short Relay Out and light the alarm LED.
Once you have finished configuring the settings, click the Apply button to apply
your configuration.
3.10.2.
Event Selection
Event Types are divided into 2 basic groups: System Events and Port Events.
System Events relate to the overall function of the switch whereas Port Events