79
Electrical connection
For air-conditioning, heating and ventilation (HVAC)
Strip connecting cables to approx. 6–8 mm as follows:
• Refer to the connection diagram
• Phase L to terminal L
• Neutral wire N to terminal N
• Voltage supply for the HVAC equipment to terminal D1
• Remove wire bridge between L and D1
• Switch wire to the consumer to terminal D2
The motion switch is ready for operation approximately
90 seconds (calibration time/warm-up time) after connec-
tion to the power supply system.
Ground connection (gnge) to terminal „
“
Connection of Consumers
High inrush currents seriously reduce the service
life of the relay. In this regard, observe the technical
information from the lighting or lamp manufacturer.
High inductive loads should be switched via an
additional relay or an additional protection.
Motion Switch
Relay/Protection
L
N
L
N
D2
D1
Heater
Fan
Power Supply
L
N
L1
N1
Load/
Consumer
GB