VIII. Maintenance

Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air
Conditioners are designed to require only the routine cleaning of air filters to assure
unimpeded air flow through the condenser heat exchanger. It is not possible to
recommend specific filter cleaning intervals since the level and the nature of airborne
particulate matter differs widely with each installation. It is generally sufficient to remove
and wash the reusable aluminum mesh air filters when the outer surfaces of these filters
appear covered with a thin layer of dust or lint. Filter recoating adhesive is recommended.
Appropriate disposable filters are available from Kooltronic.

If filter service is neglected or delayed, the air conditioner will not perform at its design
capacity. The first indication of excessively clogged air filters is usually a gradual
increase of temperature within the equipment cabinet. If operation is continued under
these conditions, the compressor will be shut off by the thermal overload device. The
compressor will restart when its external temperature drops below the protector threshold
setting and the compressor will continue to cycle on and off. Continued operation under
these conditions will cause damage, shorten compressor life and void the warranty.

A. Filter Removal and Service

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate
necessary cleaning.

CAUTION

1) Lift the filter, using the attached tab, to clear the lower filter retainer. Pull filter

toward you and downward until the top of the filter clears the upper filter retainer.

2) After removal, the filters should be flushed under warm running water with

the clean side up, driving contaminants out the dirty side of the filter. If the
accumulated dirt is oily, washing in a detergent bath is recommended, followed
by a warm water rinse as above.

3) The filters may be sprayed with Kooltronic A-16 Filter Recoating Adhesive to

trap fine airborne contaminants, or they may simply be dried and reinstalled as
strainer type filters. Recoating is recommended for best results.

4) Reinstall the filter: (a) keeping the tab at the bottom, slide filter into the upper

retainer, (b) press filter against the unit and (c) slide down into lower retainer.

Do not operate the Air Conditioner for extended periods of time with the

filter removed. The condenser coil may become clogged with dust or

lint from the air entering the face. A clogged condenser coil is not

readily detected and will give the same reaction as a clogged filter. A

clean filter is the best protection.

11

Summary of Contents for TRIMLINE K2A3C5NP33L

Page 1: ...L CAUTION BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 340...

Page 2: ...ntroduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enc...

Page 3: ...a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating t...

Page 4: ...incorrect type or amount of refrigerant will adversely affect performance and may damage the unit Make sure that these parameters are met Failure to do so may result in permanent damage to the unit MO...

Page 5: ...closure moisture accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the...

Page 6: ...TO OPERATE THE THERMOSTAT MAY NEED ADJUSTMENT Adjust Thermostat setting downward until compressor and condenser blower start Note factory setting first If unit is tested without heat load be sure to r...

Page 7: ...AB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the Air Conditioner side panel and into the M TAB To avoid misalignment of parts do not tighten any of the screws...

Page 8: ...Air Out WARM AIR RETURN FROM ENCLOSURE Enclosure opening should be located as high as possible within this area and equal or exceed size of cool air outlets COOL AIR OUTLET TO ENCLOSURE Drawings and D...

Page 9: ...models also perform at full capacity when operated at 100V 50 Hz or 200V 50 Hz respectively No transformer is required Major Component Replacements KA4C_NP33 K2A4C_NP33 K2A3C_NP33 2 000 5 000 BTU 2 0...

Page 10: ...HEATER T STAT OPTIONAL HEATER 55 T STAT 75 BU Y R THERMAL CUTOUT BU R RELAY O L C S R BK WE 2 1 CAP K2A4C_NP33 ON OFF SWITCH FOR UL LISTED UNITS CONDENSER BLR MTR 1 0 8 6 RELAY ADDITIONAL OPTIONS 1 AI...

Page 11: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet f...

Page 12: ...ss valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect ref...

Page 13: ...ntrol Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Appli...

Page 14: ...unted Cooled Mini NP33 Horizontal Accessories and Options HS P24 P47 NP36 Rack Top Panel MM NM P28 P52 NP47 Mounted Mounted Mounted SM NP17 P36 P59 NP59 H V HT WP Adapter Plate for Rack Mounting N A N...

Reviews: