Kooltronic Air Conditioners are required when the equipment operating temperature must
be kept near or lower than the ambient room temperature, and/or the cabinet must be
sealed from dust, fumes, oil, corrosives and other contaminants.This Air Conditioner utilizes
a "Closed-Loop Cooling System" to ensure optimum performance of the installed compo-
nents.

Closed-Loop cooling seals the electronics enclosure from hostile elements in the environ-
ment.Two separate circulation systems are employed.The internal system cools and dehu-
midifies the air inside the cabinet, totally isolating the sensitive electronics and other com-
ponents from the environment.The external system uses circulating ambient air or water to
discharge the heat removed from the electronics.The heat is dissipated from the enclosure
by means of the vapor compression refrigeration cycle. This takes place in a hermetically-
sealed refrigeration system, utilizing either an air-cooled or water-cooled condenser heat
exchanger. The warm air inside the enclosure is drawn through the evaporator coil where it
is cooled, dehumidified and returned.

Any enclosure moisture accumulated on the evaporator coil is collected in the condensate
tray and released to the ambient air through the drain tube or the condensate evaporator.

The heat removed through the evaporator coil is transferred by the compressed
refrigerant to the condenser coil. Ambient air or water is then passed through the
condenser coil, where it absorbs the heat and is then discharged to the environment.

Kooltronic Air Conditioners are designed to operate continuously in order to eliminate
compressor cycling, which shortens compressor life and causes line transients. The cool
air discharge temperature is regulated by the capacity control (hot gas bypass) valve.The
unit is equipped with a Low Temperature Thermostat to prevent over-cooling. In applica-
tions having frequent voluntary or involuntary power interruptions, a Short Cycle
Protector is recommended to allow adequate time for the internal pressures of the
Air Conditioner to equalize before restarting.

V. Principles of Operation

CONDENSER OUTLET

(Heated Ambient Air Out)

CONDENSER HEAT

EXCHANGER

CONDENSER AIR

INLET

(Ambient Air In)

REFRIGERANT

FILTER DRIER

CONTROL

BYPASS VALVE

METERING

DEVICE

(Capillary Tube

shown)

COMPRESSOR

EVAPORATOR

HEAT EXCHANGER

COOL AIR TO

ENCLOSURE

ACCUMULATOR

CONDENSER

AIR INLET

(Ambient Air In)

HEATED AIR FROM

ENCLOSURE

Summary of Contents for TRIMLINE K2A3C5NP33L

Page 1: ...L CAUTION BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 340...

Page 2: ...ntroduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enc...

Page 3: ...a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating t...

Page 4: ...incorrect type or amount of refrigerant will adversely affect performance and may damage the unit Make sure that these parameters are met Failure to do so may result in permanent damage to the unit MO...

Page 5: ...closure moisture accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the...

Page 6: ...TO OPERATE THE THERMOSTAT MAY NEED ADJUSTMENT Adjust Thermostat setting downward until compressor and condenser blower start Note factory setting first If unit is tested without heat load be sure to r...

Page 7: ...AB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the Air Conditioner side panel and into the M TAB To avoid misalignment of parts do not tighten any of the screws...

Page 8: ...Air Out WARM AIR RETURN FROM ENCLOSURE Enclosure opening should be located as high as possible within this area and equal or exceed size of cool air outlets COOL AIR OUTLET TO ENCLOSURE Drawings and D...

Page 9: ...models also perform at full capacity when operated at 100V 50 Hz or 200V 50 Hz respectively No transformer is required Major Component Replacements KA4C_NP33 K2A4C_NP33 K2A3C_NP33 2 000 5 000 BTU 2 0...

Page 10: ...HEATER T STAT OPTIONAL HEATER 55 T STAT 75 BU Y R THERMAL CUTOUT BU R RELAY O L C S R BK WE 2 1 CAP K2A4C_NP33 ON OFF SWITCH FOR UL LISTED UNITS CONDENSER BLR MTR 1 0 8 6 RELAY ADDITIONAL OPTIONS 1 AI...

Page 11: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet f...

Page 12: ...ss valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect ref...

Page 13: ...ntrol Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Appli...

Page 14: ...unted Cooled Mini NP33 Horizontal Accessories and Options HS P24 P47 NP36 Rack Top Panel MM NM P28 P52 NP47 Mounted Mounted Mounted SM NP17 P36 P59 NP59 H V HT WP Adapter Plate for Rack Mounting N A N...

Reviews: