IX. Trouble-Shooting

Each Kooltronic Air Conditioner is engineered for performance and built for reliability.
They are designed to require no routine maintenance other than the cleaning of ambient
air filters. If your air conditioner should require service, we have compiled a
trouble-shooting chart to assist your service personnel. If additional assistance is
required contact Kooltronic at 609 • 466-3400.

Problem

Cause

Solution

Unit not Cooling

No Power

Check Power Source and
Electrical Connections

Loss of Refrigerant

Locate and repair leak

Evaporator or Condenser

Replace Motor, Capacitor or

Blower not operating

entire Assembly

Filter clogged

Clean or replace Filter

Clogged Evaporator or

Clean Coil

Condenser Coil

Low Temperature Control

Lower setting until unit starts

(Thermostat) improperly set

Low Temperature Control

Replace Thermostat or Relay

(Thermostat) defective

when applicable

Failed Compressor

Replace Compressor

Ice on Evaporator Coil

Insufficient Heat Load or Unit

Contact Kooltronic

Oversized for Application

Failed Evaporator Blower

Replace Evaporator Blower
Motor or Assembly

Clogged Evaporator Coil

Clean Coil

Condensate draining

Enclosure not properly sealed

Check and seal all openings

continuously

Excessive opening of Enclosure

Eliminate the frequency of
door opening

Excessive vibration

Defective Motor in Blower

Replace Motor

Defective Wheel in Blower

Replace Wheel

Compressor Loose

Tighten Mounting Bolts

Compressor Inoperative

Low line Voltage

Check Nameplate Voltage
against supply

Loss of Compressor Oil

Replace Compressor

Loss of Refrigerant

Locate and repair leak

Failed Compressor Capacitor

Replace Capacitor

Thermal Overload

Contact Kooltronic

Power interruptions

Allow Compressor time to reset

Refrigerant or Oil leaks

Crack or pin hole in tubing or

Replace tubing or rebraze joint

brazed joint

13

Summary of Contents for TRIMLINE K2A3C5NP33L

Page 1: ...L CAUTION BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 340...

Page 2: ...ntroduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enc...

Page 3: ...a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating t...

Page 4: ...incorrect type or amount of refrigerant will adversely affect performance and may damage the unit Make sure that these parameters are met Failure to do so may result in permanent damage to the unit MO...

Page 5: ...closure moisture accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the...

Page 6: ...TO OPERATE THE THERMOSTAT MAY NEED ADJUSTMENT Adjust Thermostat setting downward until compressor and condenser blower start Note factory setting first If unit is tested without heat load be sure to r...

Page 7: ...AB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the Air Conditioner side panel and into the M TAB To avoid misalignment of parts do not tighten any of the screws...

Page 8: ...Air Out WARM AIR RETURN FROM ENCLOSURE Enclosure opening should be located as high as possible within this area and equal or exceed size of cool air outlets COOL AIR OUTLET TO ENCLOSURE Drawings and D...

Page 9: ...models also perform at full capacity when operated at 100V 50 Hz or 200V 50 Hz respectively No transformer is required Major Component Replacements KA4C_NP33 K2A4C_NP33 K2A3C_NP33 2 000 5 000 BTU 2 0...

Page 10: ...HEATER T STAT OPTIONAL HEATER 55 T STAT 75 BU Y R THERMAL CUTOUT BU R RELAY O L C S R BK WE 2 1 CAP K2A4C_NP33 ON OFF SWITCH FOR UL LISTED UNITS CONDENSER BLR MTR 1 0 8 6 RELAY ADDITIONAL OPTIONS 1 AI...

Page 11: ...Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet f...

Page 12: ...ss valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect ref...

Page 13: ...ntrol Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Appli...

Page 14: ...unted Cooled Mini NP33 Horizontal Accessories and Options HS P24 P47 NP36 Rack Top Panel MM NM P28 P52 NP47 Mounted Mounted Mounted SM NP17 P36 P59 NP59 H V HT WP Adapter Plate for Rack Mounting N A N...

Reviews: