CONDITIONS FOR DIESEL POWER 

PLANT PLACING OUTSIDE

2.2

FOUNDATION AND VIBRATION ISOLATION:

FOUNDATION AND VIBRATION ISOLATION:

VENTILATION:

VENTILATION:

When installing a diesel power plant outside, a properly prepared reinforced concrete foundation must 

provide a rigid support, prevent vibration and withstand the load that occurs during the operation of the 

plant. The foundation must have a depth of at least 300 mm, and a width and length greater than 400 mm 

for the size of the power plant (200 mm on each side). The foundation should be placed 200 mm above 

ground level.

When choosing an installation location, please note that the power plant is a source of hot gases.
The power plant installed outside must be located at a distance of at least 1.5 meters from the nearest 

building. The power plant must be located in accordance with the rules and local legislation.

Usually, the opening for fresh air access is located in the lower part of the premise wall, in  in this case, air 

will circulate around the entire power plant.

When installing a diesel power plant outside, the following must be provided:
- Protection from natural factors such as rain, snow, ice, precipitation with wind, flood, direct sunlight, 

freezing temperatures or excessive heat.
- Protection against air-borne pollutants such as dust, smoke, oil mist, steam, etc.
- Protection from being hit by falling objects such as trees or poles.
In this case, a necessary condition is the arrangement of a protective canopy, the distance to which must be 

at least 2 meters from the top of the power plant.

The engine exhaust contains combustion products that 

are harmful to health, be sure to remove power plant 

exhaust outside.

IMPORTANT!

void direct sunlight to avoid overheating the power 

plant.

WARNING! 

The foundation should be 20 cm wider 

than the perimeter of the power plant on 

each side

 The total height of the foundation must be 

at least 30 cm.

The foundation should be placed 20 cm 

above ground level.

The power plant must be placed at a considerable distance from the walls to ensure:

- free access to all its parts for performing maintenance or repair work;

- sufficient ventilation and fresh air supply to cool the engine and remove carbon monoxide.

Summary of Contents for KS 18-1DE-G

Page 1: ...Diesel power plant in noise absorbing housing Please read this manual before use Instruction KS 18 1XM KS 18 1YE KS 18 1DE G KS 25 3DE KS 33 3XM KS 33 3YE KS 33 3DE G EN...

Page 2: ...from flammable liquids gases at a minimum distance of 1 m Install the generator at a distance of not less than 1 m from the front control panel and not less than 50 cm on each side including the uppe...

Page 3: ...and one phase circuit breaker is prohibited ATTENTION DANGER The use of low grade fuel can lead to a degradation of the manufacturer s declared specifications or to engine failure Do not add any chemi...

Page 4: ...ocated indoors take its exhaust outside The engine exhaust contains combustion products harmful to health ATTENTION DANGER It is necessary to take into account the restriction of access to the power p...

Page 5: ...ectrician or an authorized dealer Power plant grounding is not a guaranteed protection against electric shock WARNING INDOOR POWER PLANT PLACEMENT CONDITIONS 2 1 FOUNDATION AND VIBRATION ISOLATION FOU...

Page 6: ...ulate around the entire power plant When installing a diesel power plant outside the following must be provided Protection from natural factors such as rain snow ice precipitation with wind flood dire...

Page 7: ...2 Fuel tank opening 3 Air filter 4 Fuel filter 5 Oil dipstick 6 The oil drain hole 7 Oil filling hole cover 8 Alternator 9 Exhaust pipe 10 Engine cooling radiator 11 Engine cooling fan 12 Anti vibrat...

Page 8: ...Engine speed monitoring system mechanical mechanical electronic Engine heating equipped GENERAL CHARACTERISTICS Alternator model DPC184F DPC184F DPC184F Controller Datakom D 300 Fuel tank volume l 53...

Page 9: ...2545 3170 3707 3168 Engine speed monitoring system mechanical mechanical mechanical mechanical Engine heating equipped GENERAL CHARACTERISTICS Alternator model DPC184E DPC184G DPC184G DPC184G Control...

Page 10: ...start 4 Check the battery terminals for corrosion and clean them if necessary 5 Check the control panel and power plant for dust and dirt clean if necessary 7 Clear the space around the power plant o...

Page 11: ...cation If you have any questions please contact an authorized representative of the manufacturer or an authorized dealer in your area 4 Check the battery charge if necessary charge the battery tank wi...

Page 12: ...ups are made with and buttons Each depression of the button will cause the display to switch to the next group of parameters After the last group the display will switch to the first group Each depres...

Page 13: ...ke sure that the rated power of power consumers matches with the power of generator Do not exceed the nominal power of the generator Do not connect the device before starting the engine If the power p...

Page 14: ...hree or four attempts it may mean that the fuel tank is running out of fuel Check the fuel level in the tank according to the values on the indicator IMPORTANT USING OF THREE PHASE POWER PLANT MODEL U...

Page 15: ...NUAL COMPLIANCE MANUAL COMPLIANCE Technical maintenance operation and K nner S hnen generator storage are to be performed according to this manual recommendations Manufacturer bears no responsibility...

Page 16: ...g Fan and pump belt Valve gaps Flushing the cooling system and radiator Water separator Air cleaner element Radiator rank external Fuel tank Fan belt RECOMMENDED OILS 10 fill to here fill to here Moto...

Page 17: ...t on flat level surface 2 Unscrew the oil gage cap on the engine fig 4 p 5 3 By means of a funnel pour the advanced purification engine oil to the crankcase fig 4 p 13 Oil level after filling has to b...

Page 18: ...ing with the help of an external charger To avoid discharging the battery it is recommended to run the generator at least once a month for 30 minutes If the generator is not used for a long time pleas...

Page 19: ...sel cannot be operated 6 If the external environment temperature is low use warm start up please 7 Check if the fuel pressure sensor is blocked Low battery voltage alarm LOW BATTERY VOLTAGE alarm ligh...

Page 20: ...ntrol box 3 Measure the terminal voltage of the generator with another voltage meter if it is normal then check the connection between the generator and control line Check the voltage meter and change...

Page 21: ...or misused If the claimed malfunction cannot be diagnosed or demonstrated If proper operation of the product can be restored following cleaning from dust and dirt appropriate adjustment maintenance oi...

Page 22: ......

Page 23: ...sche Fragen Kundendienst technische Fragen und Unterst tzung und Unterst tzung support dimaxgroup de Garantie Reparatur und Service Garantie Reparatur und Service service dimaxgroup de Sonstiges Sonst...

Reviews: