TP-5660 11/98
Installation 55
Kohler automatic transfer switches are shipped factory
wired and tested, ready for installation. Installation of
the switch consists of the following.
D
Unpacking and inspecting the transfer switch upon
receipt.
D
Protecting the switch against damage before and
during installation.
D
Wiring of normal source (utility), emergency
source (generator), and load circuits.
D
Wiring of control connections such as generator
start signals and accessories.
D
Checking voltages and functions.
D
Connecting and initializing the controller.
Follow this installation section first when installing the
transfer switch. Refer to the logic controller operation
and installation manual packed with the transfer switch
for details on electrical controls and accessories. See
Sections 1.3 and 1.4 for nameplate and model number
information to identify type of logic controller. See List of
Related Materials in the Introduction section in this
manual.
6.1 Upon Receipt of Unit
6.1.1
Inspection
At time of delivery, inspect the automatic transfer switch
for signs of shipping damage. If damage and/or rough
handling is evident, file a damage claim immediately
with the transportation company and promptly notify the
distributor or dealer.
6.1.2
Lifting
Unbalanced weight.
Improper lift can cause severe
injury or death and/or equipment
damage.
Use adequate lifting capacity.
Never leave transfer switch standing
upright unless it is securely bolted in
place or stabilized.
WARNING
See Figure 6-1 for the approximate weight of each
transfer switch covered in this manual. Use a spreader
bar for lifting. Attach the bar only to the enclosure’s
mounting holes or lifting brackets; do not lift the unit at
any other points. Replace, close, and lock the enclosure
door before moving or mounting the unit.
Transfer Switch
Rating
(amps)
Number of
Poles
Approximate
Weight
lb. (kg)
40
2, 3
4
237 (108)
242 (110)
80
2, 3
4
237 (108)
242 (110)
100
2, 3
4
237 (108)
242 (110)
150
2, 3
4
242 (110)
247 (112)
225
2, 3
4
242 (110)
247 (112)
260
2, 3
4
242 (110)
247 (112)
400
Any
524 (238)
600
2,3
4
638 (290)
658 (298)
800
2, 3
4
678 (308)
761 (345)
1000
3
4
678 (308)
761 (345)
1200
3
4
678 (308)
761 (345)
1600
3
4
975 (442)
1100 (499)
2000
3
4
975 (442)
1100 (499)
2500
3
4
1155 (524)
1295 (587)
3000
3
4
1155 (524)
1295 (587)
Figure 6-1. Approximate Transfer Switch Weight
Summary of Contents for ZCS series
Page 16: ...TP 5660 11 98 8 Specifications Notes...
Page 30: ...TP 5660 11 98 22 Diagrams and Drawings Notes...
Page 45: ...TP 5660 11 98 Diagrams and Drawings 37 Schematic Diagram S340 Logic 600 1200 Amp 321096 C...
Page 46: ...38 Scheduled Maintenance TP 5660 11 98 Schematic Diagram S340 Logic 1600 3000 Amp 321097 A...
Page 54: ...46 Diagrams and Drawings TP 5660 11 98 Schematic Diagram M340 Logic 600 1200 Amp 321287 C...
Page 55: ...TP 5660 11 98 Diagrams and Drawings 47 Schematic Diagram M340 Logic 1600 3000 Amp 321301 B...