TP-5660 11/98
Scheduled Maintenance 17
Section 4. Scheduled Maintenance
Scheduled preventive maintenance ensures safe and
reliable operation and extends the life of the transfer
switch.
Preventive maintenance includes periodic
testing, cleaning, inspection, and replacement of worn
or missing components.
A local authorized distributor or dealer (authorized
service center) can provide complete preventive
maintenance and services to keep the transfer switch in
top condition. Contact a local distributor or dealer for
additional information. See the Service Assistance
section in this manual for how to locate a local distributor
or dealer.
Read this entire section carefully before attempting any
maintenance or service. Unless otherwise specified,
have maintenance or service performed by an
authorized service center that has trained and qualified
personnel who follow all applicable codes and
standards.
Keep records of all maintenance or service.
Replace all barriers and close and lock the enclosure
door after maintenance or service and before reapplying
power.
Accidental starting.
Can cause severe injury or death.
Disconnect battery cables before
working on generator set. (Remove
negative
(--)
lead
first
when
disconnecting battery.
Reconnect
negative
(--)
lead
last
when
reconnecting battery.)
WARNING
Disabling the generator set. Accidental starting can
cause severe injury or death.
Before working on the
generator set or connected equipment, disable the generator
set as follows: 1) Move the generator set master switch to the
OFF position. 2) Disconnect power to the battery charger.
3) Remove battery cables, negative (--) lead first. Reconnect
negative (--) lead last when reconnecting battery. Follow these
precautions to prevent starting of generator set by an
automatic transfer switch, remote start/stop switch, or engine
start command from a remote computer.
Hazardous voltage.
Can cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(under 600 Volt)
WARNING
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening enclosure.
(600 Volt and above)
DANGER
Summary of Contents for ZCS series
Page 16: ...TP 5660 11 98 8 Specifications Notes...
Page 30: ...TP 5660 11 98 22 Diagrams and Drawings Notes...
Page 45: ...TP 5660 11 98 Diagrams and Drawings 37 Schematic Diagram S340 Logic 600 1200 Amp 321096 C...
Page 46: ...38 Scheduled Maintenance TP 5660 11 98 Schematic Diagram S340 Logic 1600 3000 Amp 321097 A...
Page 54: ...46 Diagrams and Drawings TP 5660 11 98 Schematic Diagram M340 Logic 600 1200 Amp 321287 C...
Page 55: ...TP 5660 11 98 Diagrams and Drawings 47 Schematic Diagram M340 Logic 1600 3000 Amp 321301 B...