TP-5660 11/98
56 Installation
6.1.3
Unpacking
Unpack the transfer switch immediately after receipt
and inspect for shipping damage. Failure to perform an
immediate inspection impedes recovery of losses
caused by shipping damage. Use care when unpacking
to avoid damaging any of the transfer switch
components. Remove all dirt and packing material that
may have accumulated in the transfer switch or any of its
components.
If the equipment has been stored at cold temperatures,
allow equipment to warm to room temperature for
24 hours (minimum) before unpacking to prevent
condensation on the electrical apparatus from
surrounding moist air.
6.1.4
Storage
Store the transfer switch in its protective packing until
ready for final installation.
Protect the automatic
transfer switch at all times from excessive moisture,
construction grit, and metal chips. Avoid storage in low
temperature
and
high
humidity
areas
where
condensation could occur on the unit.
6.2 Mechanical Installation
Check the System Voltage and Frequency
Do not
install a transfer switch if the system voltage and
frequency shown on the transfer switch nameplate are
different from the nominal normal (utility) source voltage
and frequency and the nominal emergency source
voltage and frequency shown on the generator set
nameplate.
To plan the installation, use the dimensions given on the
enclosure dimension drawings in Section 5. Select the
mounting site to comply with local electrical code
restrictions for the enclosure type. Mount the transfer
switch as close to the load and power sources as
possible. Allow adequate space to open the enclosure
door fully and to service the switch.
Vertically mount the 40- through 260-ampere transfer
switches covered in this manual to a wall or other rigid
vertical supporting structure.
Keyhole slots for
mounting purposes are provided in the mounting
brackets on the top and bottom of each unit. When
mounting these units, plumb the enclosure to ensure
that the door hinges are vertical to avoid any distortion of
the enclosure or door. Place washers behind the
mounting bracket key holes to shim the enclosure to a
plumb condition.
Floor mount or attach the 400-ampere transfer switch
covered in this manual to a rigid supporting structure
such as a wall. When mounting these units either way,
plumb the enclosure to ensure that the door hinges are
vertical to avoid any distortion of the enclosure or door.
For floor mounting, bolt the mounting feet to the floor
and shim the mounting feet as needed to plumb the
enclosure. Keyhole slots for wall mounting are provided
in the rear panel of the enclosure. Place washers behind
the mounting bracket key holes to shim the enclosure to
a plumb condition.
Bolt the 600- through 3000-ampere automatic transfer
switches directly to floor mounting pads. When
mounting one of these units, level the mounting pads so
that the door hinges are plumb when the unit is installed
to avoid distorting the enclosure or door.
6.3 Check Manual Operation
Follow a procedure in Section 2.3 to manually operate
the contactor but stop before reapplying power sources.
Verify that the contactor operates smoothly without
binding and prepare it for automatic operation. If the
contactor does not operate smoothly without binding,
STOP!
Call an authorized service center to service the
contactor before proceeding!
6.4 Electrical Wiring
All internal electrical connections are prewired. The
only wiring necessary when installing the transfer switch
is to connect the unit to external devices.
Observe all applicable national, state, and local
electrical codes during installation.
Install DC, control, and communication system wiring
in raceways, cables, or conduit separate from AC
power wiring.
See Section 5 for schematic diagrams and enclosure
drawings.
Accidental starting.
Can cause severe injury or death.
Disconnect battery cables before
working on generator set. (Remove
negative
(--)
lead
first
when
disconnecting battery.
Reconnect
negative
(--)
lead
last
when
reconnecting battery.)
WARNING
Summary of Contents for ZCS series
Page 16: ...TP 5660 11 98 8 Specifications Notes...
Page 30: ...TP 5660 11 98 22 Diagrams and Drawings Notes...
Page 45: ...TP 5660 11 98 Diagrams and Drawings 37 Schematic Diagram S340 Logic 600 1200 Amp 321096 C...
Page 46: ...38 Scheduled Maintenance TP 5660 11 98 Schematic Diagram S340 Logic 1600 3000 Amp 321097 A...
Page 54: ...46 Diagrams and Drawings TP 5660 11 98 Schematic Diagram M340 Logic 600 1200 Amp 321287 C...
Page 55: ...TP 5660 11 98 Diagrams and Drawings 47 Schematic Diagram M340 Logic 1600 3000 Amp 321301 B...