24
Adjust these settings according to the national or local authority Legionella Legislation
or Guidelines as appropriate for your country/area.
“Max. Warmup Time (mins)”
- The maximum time allowed for the disinfection
temperature to be reached. If the temperature is not reached within this period, then
the disinfection will be cancelled. (If unsure, leave as default.)
“Target Disinfection Time (mins)”
- The minimum disinfection cycle duration.
“Disinfection Timeout (mins)”
- The maximum duration of the cycle. If cycle is
not completed within this period, then the disinfection will be cancelled. (If unsure,
leave as default.)
“Target Temperature (C)”
- The maximum temperature required to perform a
successful disinfection cycle.
“Upper Temperature (C)”
- If the water temperature is between the
“Target
Temperature”
and the
“Upper Temperature”
, the disinfection time is progressively
reduced. The reduction is computed continuously and has the effect of halving the
time for each 5 ºC increase above the
“Target Temperature”
. Should the temperature
rise above the
“Upper Temperature”
then no further time reduction accrues.
Exposure to temperatures over 80 ºC can limit the life of the Rada Outlook product.
When all alterations are made, press
“Write”
to transfer the settings to the Control
Box and Mixer Valve.