Disinfection cycle
Warning!
Thermal disinfection mode is a potentially hazardous process!
Make sure all safety measures in this guide have been adhered to before
activating the Thermal Disinfection process.
A disinfection cycle can only be initiated when the Mixer Valve is switched off using
the
“Valve Off”
button in the
“Valve Setup”
screen.
•
Set the Disinfection Type to
“Standard Cold Inlet Supply”
or
“Exponential
Cold Inlet Supply”
depending upon the requirments for the site conditions and
perform the disinfection cycle according to the instructions in this guide.
• Reset the by-pass to normal position after the disinfection cycle has finished to
restore the cold water supply.
Press
“Arm”
to enable the disinfection feature.
Arming the disinfection cycle is confirmed when the box states
“Armed”
.
Press
“Trigger”
within 10 seconds of arming to activate the disinfection cycle.
Confirm the trigger by pressing
“OK”
.