8: Specifications
8-6
UPS413-01-00 Kohler PW 6000 (60-500kVA) User Manual 25 June 2012
8.2
60-300kVA Fuses & cables quick reference
Single feed input
Dual feed input
Note:
Battery cabling (Cable E) and battery fuses (Fuse E) are bespoke to the installation
Power (kVA)
Fuse A
(Agl/CB)
Cable A
Cable D
60
3x100
5x35
5x35
80
3x125
5x50
5x50
100
3x160
5x50
5x50
120
3x200
5x70
5x70
160
3x250
5x120 or 5x(2x50)
5x120 or 5x(2x50)
200
3x315
5x185 or 5x(2x70)
5x185 or 5x(2x70)
250
3x400
5x240 or 5x(2x95)
5x240 or 5x(2x95)
300
3x500
5x(2X120)
5x(2X120)
Power (kVA)
Fuse B
(Agl/CB)
Cable B
Fuse C
(Agl/CB)
Cable C
Cable D
60
3x100
5x35
3x100
5x35
5x35
80
3x125
5x50
3x125
5x50
5x50
100
3x160
5x50
3x160
5x50
5x50
120
3x200
5x70
3x200
5x70
5x70
160
3x250
5x120 or 5x(2x50)
3x250
5x120 or 5x(2x50)
5x120
200
3x315
5x185 or 5x(2x70)
3x315
5x185 or 5x(2x70)
5x185
250
3x400
5x240 or 5x(2x95)
3x400
5x240 or 5x(2x95)
5x240 or 5x(2x95)
300
3x500
5x(2x120)
3x500
5x(2x120)
5x(2x120)
EXTERNAL
BATTERY
Cable
E
Fuse
E
SINGLE
FEED
INPUT
(standard)
Rectifier
Inverter
Static
Switch
IA
2
Fuse
A
Cable
D
Cable
A
Mains
Supply
(3x380/400/415)
IA
1
Load
EXTERNAL
BATTERY
Cable
E
Fuse
E
DUAL
FEED
INPUT
(option)
Rectifier
Inverter
Static
Switch
IA
2
Fuse
B
Cable
D
Cable
B
IA
1
Load
Maint.
Bypass
Fuse
C
Cable
C
Mains
(3x380/400/415)
Bypass
(3x380/400/415)
F1
F2
F1
F2
Maint.
Bypass
Stati
c
By
pass
Li
n
e
Stati
c
By
pass
Li
n
e
Summary of Contents for PW 6000
Page 1: ...User Manual Pioneering solutions for total power protection Kohler PW 6000 ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Page 18: ...2 Description 2 10 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Page 52: ...4 Operation 4 14 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Page 58: ...6 Troubleshooting 6 4 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Page 74: ...8 Specifications 8 8 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...