3: Installation
3-2
UPS413-01-00 Kohler PW 6000 (60-500kVA) User Manual 25 June 2012
3.3
Unpacking
1.
If the cabinet is shipped inside a wooden case remove the screws at the base and sides of the case then
carefully remove the case from the equipment pallet.
2.
Cut the wrappers and remove the packing container by pulling it upwards.
3.
Remove the plastic sheeting covering the UPS.
4.
Remove any anchor bolts securing the cabinet to the pallet then remove the UPS from the pallet.
5.
Retain the packaging materials for possible future shipment of the UPS.
6.
Examine the UPS for signs of damage and notify your supplier immediately if any damage is found.
7.
Check that the details on the UPS nameplate corresponds to the purchased material mentioned in the
delivery note. The rating specifications can be found on a nameplate located inside the UPS door.
3.4
Storage
UPS Cabinet
If you plan to store the UPS cabinet prior to use it should be held it in a clean, dry environment with a
temperature between -5°C to +40°C and RH <90%. The UPS should be stored in the original packing and
shipping carton. If the packing container is removed you must take measures to protect the UPS from dust.
Battery
The UPS uses sealed, maintenance-free batteries whose storage capacity depends on the ambient
temperature. It is important not to store the batteries for longer than 6 months at 20°C, 3 months at 30°C, or 2
months at 35°C storage temperature without recharging them. For longer term storage the batteries should
be fully recharged every 6 months @20°C.
CAUTION: Potential dangers:
•
If the UPS/battery cabinet is tilted by more than 10° it could cause internal damage. If
tilting occurs do not connect the UPS to the mains electrical supply.
•
The weight of the UPS/battery equipment can cause serious personal injury and/or
structural damage to the surrounding area if dropped in transit. Always take extreme
care when moving the equipment.
CAUTION: Storage:
•
– The UPS should be stored in the original packing and shipping carton.
•
– The recommended storing temperature for the UPS system and batteries is between
+5°C and +40°C.
•
The UPS system and the battery sets must be protected from humidity < 90% RH
(non-condensing).
CAUTION: Sealed batteries must never be stored in a fully or partially discharged state.
Extreme temperature, under-charge, overcharge or over-discharge will destroy batteries!
•
Charge the battery both before and after storing.
•
Always store the batteries in a dry, clean, cool environment in their original packaging.
•
If the packaging is removed protect the batteries from dust and humidity.
Summary of Contents for PW 6000
Page 1: ...User Manual Pioneering solutions for total power protection Kohler PW 6000 ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Page 18: ...2 Description 2 10 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Page 52: ...4 Operation 4 14 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Page 58: ...6 Troubleshooting 6 4 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...
Page 74: ...8 Specifications 8 8 UPS413 01 00 Kohler PW 6000 60 500kVA User Manual 25 June 2012 ...