UPS413-01-00 Kohler PW 6000 (60-500kVA) User Manual 25 June 2012
4-13
4: Operation
5.
Open the module’s parallel isolator switch (IA2).
6.
Open the bypass line fuse holder F2 (IA4) and the rectifier line fuse holder F1 (IA3).
7.
Open the UPS input and bypass supply isolators (or circuit breakers) on the UPS input supply distribution
panel.
8.
The UPS is now voltage free.
WARNING:
Allow 10 minutes for the internal DC capacitors to discharge before touching the
UPS internal components.
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LED
Colour
LINE 1
Green
LINE 2
Off
BY PASS
Off
INVERTER
Off
BATTERY
Green Flashing