9: Specification
52
TS_610_01 PowerWAVE 6000 S3 (60-120kVA) User Manual 21/10/19
Rated short time withstand current
10kA for 1.5 seconds
AC Power distribution system
TN-S, TN-C, TN-C-S, TT
Required input connection
3 phases an neutral required
BATTERY CHARACTERISTICS
60
80
100
120
Battery type
Maintenance-free VRLA, vented lead-acid, NiCd
Variable number of 12V battery blocks
No.
42-48
Autonomies >60 min are only available for loads < 90%.
For loads between 90-100%, the maximum allowed autonomy is 60 mins.
For autonomy's less than 20 mins UPS supports 42-50 x12 V blocks
Variable number of 1.2V NiCd cells
No.
420-480
Autonomies >60 min are only available for loads < 90%.
For loads between 90-100%, the maximum allowed autonomy is 60 mins.
For autonomy's less than 20 mins UPS supports 420-500 x1.2V cells
Max. battery charger current
A
37
49
61
61
Max. battery charger power
kW
18
24
30
30
Battery float voltage (VRLA / NiCd)
VDC 2.25 / 1.40
End of discharge voltage (VRLA / NiCd)
VDC 1.65 / 1.05
Temperature controlled charger
Yes (temperature sensor optional)
Ripple current (rms)
%
2% of the battery capacity
Battery test
Automatic and periodic (adjustable)
OUTPUT CHARACTERISTICS
60
80
100
120
Output rated power
(@min 42 battery blocks)
kVA/
kW
60/60
80/80
100/100
120/120
Load power factor rated
1.0
Output current (In)
(PF=1.0) (@min 42 battery blocks)
A
87
116
145
174
Output rated voltage
V
3x 380/220 or 3x 400/230 or 3x 415/250
Output waveform
Sinewave with 0deg. phase imbalance @100% unbalanced load
Output voltage stability (normal/battery mode)
%
± 1.5 / ± 1.5
Total harmonic distortion with 100% load
operating in normal mode
%
< 2 with linear load
Total harmonic distortion with 100% load
operating in battery mode
%
< 2 with linear load
Voltage transient and recovery time with
100% step load
%/
sec
< 4% (linear load)
Output frequency
Hz
50 or 60
Output frequency tolerance
%
±0.1 free-running, quartz oscillator
±2 or ±4 (selectable) with mains synchronised
Frequency slew rate
Hz/s
1.0
Max synch phase error
°
< 2° (referred to a 360° cycle)
Permissible unbalanced load
%
100% (all 3 phases independently regulated)
Overload capability on inverter
% /
min
150% load for 30 seconds
125% load for 5 minutes
110% load for 20 minutes
Fault clearing capability (100ms)
A
2x In for normal mode and battery mode
Bypass short circuit capability
A
10x rated In for 10ms
INPUT CHARACTERISTICS (Continued)
60
80
100
120