![Kohler PowerWAVE 6000 User Manual Download Page 22](http://html1.mh-extra.com/html/kohler/powerwave-6000/powerwave-6000_user-manual_1990174022.webp)
2: General Description
14
TS_610_01 PowerWAVE 6000 S3 (60-120kVA) User Manual 21/10/19
2.6.3 Power Management Display (PMD)
Working in conjunction with the
UP
,
DOWN
and
ENTER
buttons, the LCD screen at the centre of the power management
display presents a range of selectable menus which allows the user to operate the UPS and monitor its performance – the
menu tree is shown in Figure 2.10.
Status screens
During normal operation the LCD displays a default UPS status screen similar to those shown below. From the status
screen the user can access the ‘top level’ menu by pressing the
UP
or
DOWN
button; and then further navigate through the
nested sub-menus using the
UP
or
DOWN
buttons to scroll, and the
ENTER
button to make a selection.
On the right hand side of the LCD-Display is a three digit indicator which shows the module’s position in a multi-module
system (maximum number of modules is 10).
Top level menu
The following sub-menus can be accessed from the top level menu:
EVENT
LOG
– The event log stores the last 64 UPS events in date/time stamp order. These include both ‘fault’ events,
such as [
OVERLOAD
], and ‘operational’ events such as [
LOAD
TO
BYP.
].
MEASUREMENTS
– This sub menu provides access to a range of input, output and battery parameter metering.
COMMANDS
– This sub menu provides access to a range of commands that might be used during day-to-day UPS
operation. Those most commonly accessed are the [
LOAD
TO
INVERTER
] and [
LOAD
TO
BYPASS
] command which are
used to transfer the load between inverter and bypass during the UPS start-up and shut down procedures.
– [
PERFORM
BATT
.
TEST
] Stops the charger and monitors the off-load battery voltage for 1 min. then transfers the load to
battery for a further 1 min.
– [
PERFORM DEEP
BATT
.
TEST
] Performs as above, but runs with battery on load until the low voltage alarm activates.
SET-UP
DATA
– This is a read-only menu and shows the UPS details input by the manufacturer/commissioning engineer.
– [
DYNAMIC
PASSWORD
] is normally set to
NO
SET-UP
USER
– This sub menu allows the user to select the LCD display language, set the local date/time used to stamp
the Event Log, set up the automatic battery test operation and configure the UPS options when running on standby
generator.
SET-UP
SERVICE
– This menu is used by the commissioning engineer and is password-protected to restrict access.
This status screen indicates that the UPS is operating ‘on inverter’ and
providing protected power to the load.
LOAD
P01
PROTECTED
This status screen indicates that the UPS will not support the load during a
power failure, examples include 'on bypass' or batteries disconnected
LOAD
P01
NOT PROTECTED
This status screen indicates that the load is not being powered from the UPS,
usually because the UPS has been switched off by the
ON/OFF
buttons.
LOAD OFF
P01
SUPPLY FAILURE
This status screen indicates that the UPS parallel switch (IA2) is open and
the UPS module is disconnected from the parallel system. Although in a
redundant parallel system the load might still be receiving protected power
from the remaining on-line modules.
LOAD DISCONNECTED
P02
PARALLEL SWITCH OPEN
S
Stands for
S
ingle unit. The UPS system comprises only one cabinet.
P01
Stands for
P
arallel system and 01 identifies the cabinet as the 1st module (MASTER) in the system.
P02
Stands for
P
arallel system and 02 identifies the cabinet as the 2nd module (SLAVE) in the system.
This number can range from 02 to 10 depending on the cabinet’s position in the parallel system.