TS_610_01 PowerWAVE 6000 S3 (60-120kVA) User Manual 21/10/19
37
5: Operating Instructions
18. On the module control panel:
a) Press the
UP
key once to access the menu system.
b) Use the
UP/DOWN
keys to move the cursor so that it is adjacent to
COMMANDS
and then press the
ENTER
key.
c) Use the
UP/DOWN
keys to move the cursor so that it is adjacent to
LOAD
TO
INVERTER
and then press the
ENTER
key.
19. The UPS module output should transfer to inverter.
20. On the module control panel (of ALL modules) verify that:
d) The
BYPASS
LED is extinguished.
e) The
INVERTER
LED changes to green.
5.3
How to start the UPS system from the maintenance bypass
Initial conditions:
This procedure assumes the following initial conditions.
• The UPS input and bypass mains supplies are turned ON at the switchgear panel.
• The load equipment is turned on and receiving power through the UPS maintenance bypass.
Powering up the UPS system:
If the UPS system is operating on maintenance bypass it can be powered up using the procedure described in
paragraph 5.2 (
"How to start the UPS system from a fully powered-down condition"
) beginning at step 7.
Key Point:
The UPS System is now in its ‘on inverter’ operating mode and providing the load with processed,
protected power.
Key Point:
If the load is not already turned on, turn it on now, while the UPS system is operating on
maintenance bypass, before you continue with this procedure.
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD