5: Operating Instructions
42
TS_610_01 PowerWAVE 6000 S3 (60-120kVA) User Manual 21/10/19
Module shutdown:
1. Turn
OFF
the UPS module by pressing both
ON/OFF
buttons simultaneously
then releasing them.
a) The module control panel will display
LOAD OFF
and
SUPPLY
FAILURE.
b) The module control panel mimic indications should be as shown here.
2. Open the module’s parallel switch (IA2).
3. Open the battery fuses/breaker located in the external battery cabinet/rack.
a) The
BATTERY
led on the module mimic should change to flashing green.
b) The module control panel mimic indications should be as shown here.
4. Open the UPS input isolator (IA3) and bypass isolator (IA4).
a) The module is now fully powered down.
Module start-up:
1. Close the UPS input isolator (IA3) and bypass isolator (IA4).
2. Close the module’s parallel switch (IA2).
3. Close the battery fuses/breaker located in the external battery cabinet/rack.
a) The module control panel will display
LOAD OFF, SUPPLY FAILURE.
b) The
BATTERY
led on the module control panel mimic should change
from flashing to permanent green.
c) The module control panel mimic indications should be as shown here.
4. Turn
ON
the UPS module by simultaneously pressing both
ON/OFF
buttons
then releasing them.
a) The UPS module(s) will start-up over about 60 seconds.
b) The
INVERTER
will start-up and come on line (Green).
c) The module control panel will display
LOAD PROTECTED
.
d) The module control panel mimic indications should be as shown here.
WARNING:
The UPS module is still live at its input and output power terminals. Allow 10 minutes for the
internal DC capacitors to discharge before touching any UPS internal components.