TS_610_01 PowerWAVE 6000 S3 (60-120kVA) User Manual 21/10/19
41
5: Operating Instructions
4. On the module control panel(s), verify that:
a) The
INVERTER
LED has extinguished.
b) The
BYPASS
LED is green.
c) The LCD displays
LOAD NOT PROTECTED
.
Transfer the UPS system from ECO (‘on bypass’) mode to ‘on inverter’ mode:
5. On the module control panel (on any module in a parallel system):
a) Press the
UP
key once to access the menu system.
b) Use the
UP/DOWN
keys to move the cursor so that it is adjacent to
COMMANDS
and then press the
ENTER
key.
c) Use the
UP/DOWN
keys to move the cursor so that it is adjacent to
LOAD TO INVERTER
and then press the
ENTER
key.
d) The UPS module output should transfer to inverter.
6. On the module control panel(s), verify that:
a) The
BYPASS
LED has extinguished.
b) The
INVERTER
LED is green.
c) The LCD displays
LOAD PROTECTED
.
5.7
Individual module stop/start procedure (redundant parallel system)
As described earlier in this manual, if a parallel module UPS system includes module redundancy an individual UPS
module can be shut down without affecting the overall system operation. The situations where this might be put into effect
are usually managed by a qualified service engineer when undertaking service repairs; however, under certain
circumstances there may be a case for this to be carried out by the user. For example, if a large proportion of the load is to
be shut down for a significant period the number of on-line modules in the UPS system might be reduced to save on the
utility power demands.
WARNING:
The load will be transferred to bypass and not supported by the UPS system if:
• You turn off the module in a standalone system, or
• You turn off a module in a capacity rated system (which may overload the remaining on-line modules).
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD