Restore the generator set to service.

7.1

Check that the generator set master switch is in
the OFF position.

7.2

Reconnect the generator set engine starting
battery, negative (--) lead last.

7.3

Reconnect power to the battery charger, if
equipped.

7.4

Move the generator set master switch to the
AUTO position for startup by a remote transfer
switch or remote start/stop switch.

Move the

remote annunciator alarm horn switch to the
NORMAL position. If the horn sounds or a lamp
illuminates,

see

step

8

for

the

resetting

instructions.

8.

Resetting the generator set controller and
remote annunciator.

Use the following procedure to reset the controller
and the remote annunciator after a fault alarm.

8.1

Press the ALARM OFF key on the controller
keypad to silence the controller alarm horn.

8.2

Move the remote annunciator alarm horn switch to
SILENCE to stop the alarm horn. The respective
remote annunciator lamp remains lit.

8.3

Disconnect the generator set from the system load
with the line circuit breaker or the automatic
transfer switch.

8.4

Correct the cause of the fault alarm (refer to the
generator set service manual).

8.5

Move the generator set master switch to the
OFF/RESET position and then to the RUN
position for startup.

The remote annunciator

alarm horn and the controller alarm horn sound
because the unit is not in the AUTO position. The
remote annunciator Generator Switch Not in Auto
lamp lights.

8.6

Verify that the cause of the alarm has been
corrected.

8.7

Reconnect the generator set to the system load
via the line circuit breaker or automatic transfer
switch.

8.8

Move the generator set master switch to the
AUTO position for startup by the remote transfer
switch or the remote start/stop switch.

8.9

Move the remote annunciator alarm horn switch to
the NORMAL position.

Summary of Contents for GM17071-KP1

Page 1: ...stations Read the entire installation procedure and compare the kit parts with the parts list in this publication before beginning installation Perform the steps in the order shown Observe applicable...

Page 2: ...temperature shuts down the generator set Line Power The lamp illuminates when commercial utility power or other source supplies the power when equipped with an auxiliary contact When the lamp illumina...

Page 3: ...pped 1 3 Disconnect the generator set engine starting battery ies negative lead first 2 Mount and connect the controller connection assembly 2 1 GM17070 KP1 and GM17070 KP1S kits 20 300 kW 2 1 1 Remov...

Page 4: ...access door 2 3 3 Attach the controller connection assembly GM13984 to the junction box inner panel studs using six spacers X 712 9 and nuts X 70 12 Place the spacers between the controller connection...

Page 5: ...location D An area as near to the generator set controller as practical 3 2 Remove the four cover screws X 6216 1 and lift the box cover 256880 to access the internal components 3 3 Mount the 14 relay...

Page 6: ...5 16 in diameter or X 283 32 1 2 in diameter as required Do not use terminals 42A and 2 on the 14 relay dry contact box terminal strip to supply voltage to the relay contacts The user must attach sep...

Page 7: ...ctrical box in the wall See Figure 8 for the mounting hole dimensions Protect the remote annunciator from dust and debris when drilling the holes Note Use mounting hardware suitable for the wall compo...

Page 8: ...total wire length for each conductor is 122 m 400 ft According to the chart in Figure 9 this example requires 14 gauge wire for leads N and 42B only Use stranded or solid 18 or 20 gauge wire for signa...

Page 9: ...Pressure RDO8 K12 Input K12 NO terminal 63 Low Water Temperature RDO5 K13 Input K13 NO terminal 35 High Engine Temperature Warning RDO6 K14 Input K14 NO terminal 40 Figure 10 Remote Annunciator Kit W...

Page 10: ...Move the remote annunciator alarm horn switch to SILENCE to stop the alarm horn The respective remote annunciator lamp remains lit 8 3 Disconnect the generator set from the system load with the line c...

Page 11: ...ing 0 688 x 0 875 in NPT X 634 11 1 Bushing 0 938 x 1 187 in NPT X 634 14 2 Rivet pop 1 8 diameter Al Al X 781 21 4 Screw 10 24 x 0 50 in X 6216 1 1 Fuse 10 amp 223316 1 Box dry contact 226676 1 Holde...

Page 12: ...1 Bushing 0 688 x 0 875 in NPT X 634 11 1 Bushing 0 938 x 1 187 in NPT X 634 14 2 Rivet pop 1 8 diameter Al Al X 781 21 4 Screw 10 24 x 0 50 in X 6216 1 1 Fuse 10 amp 223316 1 Box dry contact 226676...

Reviews: