10
TT-1303
7/02
7.
Restore the generator set to service.
7.1
Check that the generator set master switch is in
the OFF position.
7.2
Reconnect the generator set engine starting
battery, negative (--) lead last.
7.3
Reconnect power to the battery charger, if
equipped.
7.4
Move the generator set master switch to the
AUTO position for startup by a remote transfer
switch or remote start/stop switch.
Move the
remote annunciator alarm horn switch to the
NORMAL position. If the horn sounds or a lamp
illuminates,
see
step
8
for
the
resetting
instructions.
8.
Resetting the generator set controller and
remote annunciator.
Use the following procedure to reset the controller
and the remote annunciator after a fault alarm.
8.1
Press the ALARM OFF key on the controller
keypad to silence the controller alarm horn.
8.2
Move the remote annunciator alarm horn switch to
SILENCE to stop the alarm horn. The respective
remote annunciator lamp remains lit.
8.3
Disconnect the generator set from the system load
with the line circuit breaker or the automatic
transfer switch.
8.4
Correct the cause of the fault alarm (refer to the
generator set service manual).
8.5
Move the generator set master switch to the
OFF/RESET position and then to the RUN
position for startup.
The remote annunciator
alarm horn and the controller alarm horn sound
because the unit is not in the AUTO position. The
remote annunciator Generator Switch Not in Auto
lamp lights.
8.6
Verify that the cause of the alarm has been
corrected.
8.7
Reconnect the generator set to the system load
via the line circuit breaker or automatic transfer
switch.
8.8
Move the generator set master switch to the
AUTO position for startup by the remote transfer
switch or the remote start/stop switch.
8.9
Move the remote annunciator alarm horn switch to
the NORMAL position.